Notes |
Date |
Text |
2020-01-26 12:54:09 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND | | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS | | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC | | 109.3 | | 2. PROVIDE EXTERIOR LIGHTING CONTROLS AS SPECIFIED IN | | THE FBC ENERGY CONSERVATION. FBC EC C405.2.5 | | 3. PROVIDE EQUIPMENT GROUNDING CONDUCTOR TO SIGN. NEC | | 600.7 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH | | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL | | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. | | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD | | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|