2020-01-02 18:55:09 | 01/02/2020 1ST POOL REVIEW **DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. POOL GAS HEATER DOES NOT HAVE THE MODEL OR SIZE, |
| PLEASE PROVIDE ON SHEET 1 OR HIGHLIGHT ON SPECS PER THE |
| WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| 2. THE POOL HEATER SHALL HAVE A MINIMUM THERMAL |
| EFFICIENCY OF 82% PER THE 2017 FBC-ENERGY SEC. |
| R403.10.4. |
| 3. THERE IS A COLLECTOR TANK ON A RESIDENTIAL POOL, |
| PLEASE CLARIFY THE REASON FOR THE INSTALLATION OF THIS |
| APERTURE ON THIS SYSTEM PER THE WPB AMENDMENTS TO THE |
| FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| 4. MAIN DRAIN SYSTEM AND SERVICE OVERFLOW SYSTEMS WITH |
| DISCHARGE TO COLLECTOR TANKS SHALL BE SIZED A MAXIMUM |
| 3' PER SECOND AND IT IS SHOWING 3.9' PER SECOND AS IT |
| NEEDS TO MEET THE SAME CRITERIA OF THE CODE PER THE |
| 2017 FBC SEC. 454.1.6.5.8 SWIMMING POOLS AND BATHING |
| PLACES (PUBLIC AND PRIVATE) . |
| 5. DOES THE COLLECTOR TANK HAVE A DRAINING SYSTEM AND |
| HOW IS THE COLLECTOR TANK GOING TO BE CLEAN OR |
| SERVICED, PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE |
| FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| LUIS A. CRESPO |
| PLUMBING INSPECTOR / |
| PLUMBING PLAN REVIEW |
| AVAILABLE FROM 1:00 PM TO 4:00 PM |
| [email protected] |
| 561-805-6720 |
| |
| |