Plan Review Notes
Plan Review Notes For Permit 19121035
Permit Number 19121035
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-01-15 12:36:26THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS NO LIFE SAFETY PLAN INDICATING REQUIRED
 EGRESS CAPACIY IS MET, INCLUDING THE IMPACT OF EGRESS
 INCREASES ON ADJACENT EXISTING EGRESS ROUTES.
  
 PER NFPA 1
  
 4.1.3.2.2.3 BUILDINGS SHALL BE DESIGNED AND CONSTRUCTED
 TO PROVIDE
 REASONABLE LIFE SAFETY FOR OCCUPANTS AND WORKERS DURING
 CONSTRUCTION AND DEMOLITION.
  
 4.4.3.1 UNOBSTRUCTED EGRESS.
 4.4.3.1.1 IN EVERY OCCUPIED BUILDING OR STRUCTURE,
 MEANS OF
 EGRESS FROM ALL PARTS OF THE BUILDING SHALL BE
 MAINTAINED FREE AND
 UNOBSTRUCTED.
  
 4.4.3.1.3 MEANS OF EGRESS SHALL BE ACCESSIBLE TO THE
 EXTENT
 NECESSARY TO ENSURE REASONABLE SAFETY FOR OCCUPANTS
 HAVING
 IMPAIRED MOBILITY.
 4.4.3.2 AWARENESS OF EGRESS SYSTEM.
 4.4.3.2.1 EVERY EXIT SHALL BE CLEARLY VISIBLE, OR THE
 ROUTE TO REACH
 EVERY EXIT SHALL BE CONSPICUOUSLY INDICATED.
 4.4.3.2.2 EACH MEANS OF EGRESS, IN ITS ENTIRETY, SHALL
 BE ARRANGED
 OR MARKED SO THAT THE WAY TO A PLACE OF SAFETY IS
 INDICATED IN A
 CLEAR MANNER.
  
 4.5.6 CONSTRUCTION, REPAIR, AND IMPROVEMENT OPERATIONS.
 4.5.6.1 BUILDINGS OR PORTIONS OF BUILDINGS SHALL BE
 PERMITTED TO BE
 OCCUPIED DURING CONSTRUCTION, REPAIR, ALTERATIONS, OR
 ADDITIONS ONLY
 WHERE REQUIRED MEANS OF EGRESS AND REQUIRED FIRE
 PROTECTION
 FEATURES ARE IN PLACE AND CONTINUOUSLY MAINTAINED FOR
 THE PORTION
 OCCUPIED OR WHERE ALTERNATIVE LIFE SAFETY MEASURES AND
 BUILDING
 PROTECTION MEASURES ACCEPTABLE TO THE AHJ ARE IN PLACE.
  
 NFPA 101
  
 4.6.10 CONSTRUCTION, REPAIR, AND IMPROVEMENT
 OPERATIONS.
 4.6.10.1* BUILDINGS, OR PORTIONS OF BUILDINGS, SHALL BE
 PERMITTED TO
 BE OCCUPIED DURING CONSTRUCTION, REPAIR, ALTERATIONS,
 OR ADDITIONS
 ONLY WHERE REQUIRED MEANS OF EGRESS AND REQUIRED FIRE
 PROTECTION
 FEATURES ARE IN PLACE AND CONTINUOUSLY MAINTAINED FOR
 THE PORTION
 OCCUPIED OR WHERE ALTERNATIVE LIFE SAFETY MEASURES
 ACCEPTABLE TO
 THE AUTHORITY HAVING JURISDICTION ARE IN PLACE.
 4.6.10.2* IN BUILDINGS UNDER CONSTRUCTION, ADEQUATE
 ESCAPE
 FACILITIES SHALL BE MAINTAINED AT ALL TIMES FOR THE USE
 OF
 CONSTRUCTION WORKERS. ESCAPE FACILITIES SHALL CONSIST
 OF DOORS,
 WALKWAYS, STAIRS, RAMPS, FIRE ESCAPES, LADDERS, OR
 OTHER APPROVED
 MEANS OR DEVICES ARRANGED IN ACCORDANCE WITH THE
 GENERAL
 PRINCIPLES OF THE CODE INSOFAR AS THEY CAN REASONABLY
 BE APPLIED
 TO BUILDINGS UNDER CONSTRUCTION
  
 PLEASE PROVIDE DETAILS
  
  
 2) SHEET A 108 - THERE ARE NO INDIACTIONS OF EXIT
 HARDWARE, LOCKS OR LATCHES.
  
 PER NFPA 101, CH 12
  
 12.2.2.2 DOORS.
 12.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 12.2.2.2.2 ASSEMBLY OCCUPANCIES WITH OCCUPANT LOADS OF
 300 OR LESS IN
 MALLS (SEE 36.4.4.4.2(4) SHALL BE PERMITTED TO HAVE
 HORIZONTAL OR VERTICAL
 SECURITY GRILLES OR DOORS COMPLYING WITH 7.2.1.4.1(3)
 ON THE MAIN
 ENTRANCE/EXITS.
 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM
 AN AREA HAVING
 AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE
 PERMITTED TO BE
 PROVIDED WITH A LATCH OR LOCK ONLY IF THE LATCH OR LOCK
 IS PANIC
 HARDWARE OR FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7,
 UNLESS
 OTHERWISE PERMITTED BY ONE OF THE FOLLOWING:
 (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS
 LOCKS AS
 PERMITTED IN 12.2.2.2.5.
 (2) THIS REQUIREMENT SHALL NOT APPLY TO
 ACCESS-CONTROLLED EGRESS DOORS
 AS PERMITTED IN 12.2.2.2.6.
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE OR A DETAILED
 NARRATIVE, INCLUDING MANUFACTURUES'S SPECIFICATION
 SHEETS, WITH SPECIFIC CODE REFERENCES.
  
  
 3) SHEET A 108 & E 1 - HOW WILL THE EXIT AND EXIT
 ACCESS BE MARKED AND ILLUMINATED.
  
 PER NFPA CH 12
  
 12.2.10 MARKING OF MEANS OF EGRESS.
 12.2.10.1 MEANS OF EGRESS SHALL BE PROVIDED WITH SIGNS
 IN
 ACCORDANCE WITH SECTION 7.10.
  
 12.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF
 EGRESS, OTHER HAN FOR PRIVATE PARTY TENTS NOT EXCEEDING
 1200 FT2 (112 M2) , SHALL
 BE ILLUMINATED IN ACCORDANCE WITH SECTION 7.8.
 12.2.9 EMERGENCY LIGHTING.
 12.2.9.1 EMERGENCY LIGHTING SHALL BE PROVIDED IN
 ACCORDANCE WITH
 SECTION 7.9.
  
 PLEASE PROVIDE DETAILS
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  