2020-02-14 15:01:25 | COURTYARD RENOVATION |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| |
| CORRECTIONS NEEDED - |
| 1) THE ENCLOSED COURT YARD HAS ADDED OCCUPANT LOAD TO |
| THE BUILDING AS A WHOLE. PLEASE PROVIDE A LIFE SAFETY |
| PLAN FOR THE ENTIRE BUILDING SHOWING ALL EGRESS |
| COMPONENTS, OCCUPANT LOAD, MEANS OF EGRESS, EXIT ACCESS |
| TRAVEL DISTANCE, EXIT WIDTHS ETC. FBC 1004.1 |
| 2) PLEASE SHOW THE EXIT GATES/DOORS SEPARATION TO |
| COMPLY WITH FBC 1007 |
| 3) 3 OR MORE EXITS FROM THE ADDED COURTYARD MAY BE |
| REQUIRED PER FBC 1006.2.1.1 (OCCUPANT LOAD NEEDS TO BE |
| BASED ON USE OF THE SPACE PER FBC 1004 - NOT WHAT YOU |
| SAY AS "ACTUAL". |
| 4) PLEASE SHOW EXIT SIGNAGE AT EACH REQUIRED EXIT PER |
| FBC 1013.1 |
| 5) PLEASE SHOW THE " FUNCTION OF THE SPACE" FOR THE |
| COURTYARD PER FBC 1004.1.2 |
| 6) PLEASE STATE ON THE DRAWINGS THAT THE OCCUPANT LOAD |
| SHALL BE POSTED PER FBC 1004.3 |
| 7) PLEASE PROVIDE SPECS FOR THE "PANIC HARDWARE" TO |
| COMPLY WITH FBC 1010.1.10.1 |
| 8) PLEASE PROVIDE A STATEMENT ON THE DRAWINGS THAT THE |
| ELECTROMAGNETICALLY LOCKED GATES/DOORS SHALL RELEASE BY |
| THE PUSH OF THE PANIC HARDWARE PER FBC 1010.1.9.9 (5) |
| 9) PLEASE SHOW ALL WALKING AREAS TO COMPLY WITH FBC |
| ACCESSIBILITY (ACCESSIBLE ROUTES ETC.) CHAPTER 4 |
| 10) PLEASE PROVIDE A SOIL REPORT FBC 1803.2 |
| 11) PLEASE PROVIDE EXTERIOR PERIMETER WALL DETAILS. FBC |
| WPB AMENDMENTS 107 |
| 12) "SCULPTURAL STRUCTURAL DRAWINGS" AND "ELECTRICAL" |
| DRAWINGS DO NOT SHOW IN "ADOBE" AS ELECTRONICALLY |
| SIGNED. THIS WILL NEED TO BE CORRECTED. |