2020-01-02 11:52:53 | PLAN REVIEW - NFIP |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| BUILDING PLANS EXAMINER, PX3169 |
| 1&2 FAMILY PLANS EXAMINER, SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. SECTION A4 STATES BUILDING USE AS RESIDENTIAL. THIS |
| SHOULD STATE - ADDITION TO EXISTING RESIDENTIAL |
| BUILDING. |
| |
| 2. SECTION B9 STATES BASE FLOOD ELEVATION OF 6. THE |
| STRUCTURE IS LOCATED IN A SPECIAL FLOOD HAZARD AREA |
| THAT INCLUDES TWO BASE FLOOD ELEVATIONS - AE6 & AE7. |
| ENTER BOTH 6 & 7 IN B9. |
| |
| 3. SECTION C2 STATES LOWEST ELEVATION OF MACHINERY IS |
| AT 6.7 NAVD88. ALL EQUIPMENT SERVICES THE BUILDING |
| SHALL BE RAISED TO THE BASE FLOOD ELEVATION OF 6 FEET |
| NAVD PLUS ONE FOOT OF FREEBOARD. MINIMUM ELEVATION TO |
| THE BOTTOM OF ALL EQUIPMENT SEVICEING THE BUILDING |
| SHALL BE 7.0 FEET NAVD88. |
| |
| 4. PHOTO NUMBER ONE ON PAGE 6 OF 6 IS NOT APPLICABLE TO |
| THIS PERMIT. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| |
| |
| |