Plan Review Notes
Plan Review Notes For Permit 19120974
Permit Number 19120974
Review Stop NFIP
Sequence Number 1
Notes
Date Text
2020-01-02 11:52:53PLAN REVIEW - NFIP
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SECTION A4 STATES BUILDING USE AS RESIDENTIAL. THIS
 SHOULD STATE - ADDITION TO EXISTING RESIDENTIAL
 BUILDING.
  
 2. SECTION B9 STATES BASE FLOOD ELEVATION OF 6. THE
 STRUCTURE IS LOCATED IN A SPECIAL FLOOD HAZARD AREA
 THAT INCLUDES TWO BASE FLOOD ELEVATIONS - AE6 & AE7.
 ENTER BOTH 6 & 7 IN B9.
  
 3. SECTION C2 STATES LOWEST ELEVATION OF MACHINERY IS
 AT 6.7 NAVD88. ALL EQUIPMENT SERVICES THE BUILDING
 SHALL BE RAISED TO THE BASE FLOOD ELEVATION OF 6 FEET
 NAVD PLUS ONE FOOT OF FREEBOARD. MINIMUM ELEVATION TO
 THE BOTTOM OF ALL EQUIPMENT SEVICEING THE BUILDING
 SHALL BE 7.0 FEET NAVD88.
  
 4. PHOTO NUMBER ONE ON PAGE 6 OF 6 IS NOT APPLICABLE TO
 THIS PERMIT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  