Plan Review Notes For Permit 19120883 |
Permit Number |
19120883 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-01-03 09:25:33 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) PROVIDE TWO SETS OF A GENERATOR PAD DETAIL DRAWING. | | SPECIFY THE LENGTH, WIDTH AND THICHNESS OF THE CONCRETE | | SLAB. SPECIFY THE STEEL REINFORCING IN THE SLAB AND THE | | TYPE AND SIZE OF THE ANCHORS THAT WILL ATTACH THE | | GENERATOR TO THE SLAB. SOME OF THIS INFORMATION WAS | | PROVIDED ON THE ELECTRIAL PLANS. NOTE #1 ON PAGE 8 OF | | THE GENERAC INSTALLATION LAYOUT LISTS THE RECOMMENDED | | CONCRETE PAD SIZE. PLEASE PROVIDE ALL OF THIS | | INFORMATION ON THE GENERATOR PAD DETAIL DRAWINGS ALONG | | WITH THE PROPERTY ADDRESS AND THE PRINTED NAME AND | | SIGNATURE OF THE PERSON THAT DID THE DRAWING. FBC | | 107.2.1 | | |
|