2020-01-03 09:25:33PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE TWO SETS OF A GENERATOR PAD DETAIL DRAWING.
 SPECIFY THE LENGTH, WIDTH AND THICHNESS OF THE CONCRETE
 SLAB. SPECIFY THE STEEL REINFORCING IN THE SLAB AND THE
 TYPE AND SIZE OF THE ANCHORS THAT WILL ATTACH THE
 GENERATOR TO THE SLAB. SOME OF THIS INFORMATION WAS
 PROVIDED ON THE ELECTRIAL PLANS. NOTE #1 ON PAGE 8 OF
 THE GENERAC INSTALLATION LAYOUT LISTS THE RECOMMENDED
 CONCRETE PAD SIZE. PLEASE PROVIDE ALL OF THIS
 INFORMATION ON THE GENERATOR PAD DETAIL DRAWINGS ALONG
 WITH THE PROPERTY ADDRESS AND THE PRINTED NAME AND
 SIGNATURE OF THE PERSON THAT DID THE DRAWING. FBC
 107.2.1
  