2020-01-06 14:32:27 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 19120832 |
| ADD: 801 N OLIVE SUITE: 1209 |
| CONT: J D ROOFING AND CONTRACTING |
| TEL: 561-719-0725 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION. |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MONDAY JAN. 06/ 2020 |
| ACTION: DENIED |
| |
| 1) PLEASE NOTE THIS IS A HIGHRISE CONDO AND THE |
| REQUIREMENTS FOR FLOORING ARE VERY STRINGENT. THE ONLY |
| REFERENCE TO THE TYPE OF FLOORING BEING INSTALLED IS |
| THE PERMIT APPLICATION, THE PERMIT APPLICATION |
| INDICATES THE NEW FLOORING BEING INSTALLED IS WALNUT. |
| THERE IS NO OTHER INFORMATION PROVIDED. IS THE WALNUT |
| FLOORING A LAMINATE, ENGINEERED WOOD OR A ? INCH THICK |
| PLANK FLOORING? THE SECOND ISSUE IS THE FLOORING |
| INSULATION APPROVALS ARE FOR SOUND LVT VINYL ON |
| SILENCER LVT UNDERLAYMENT. PLEASE PROVIDE THE TYPE OF |
| WALNUT FLOORING AND UNDERLAYMENT THAT IS TO BE |
| INSTALLED AND TESTED TO THE 3 TEST LISTED BELOW. WE |
| WANT THE ACTUAL TEST NOT SALES BROCHURES. IF THE WALNUT |
| FLOORING IS ? INCH PLANK FLOORING AND SUBFLOOR AND OR |
| SLEEPERS ARE TO BE INSTALLED THEN COMPLIANCE NEEDS TO |
| FOLLOW 805.1 OF THE FBC-B 2017 CODE FOR TYPE I TYPE II |
| BUILDINGS. |
| |
| BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| 2017) |
| FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL |
| NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| PLEASE PROVIDE TEST REPORTS (NOT SALES BROCHURES) |
| SHOWING COMPLIANCE WITH: |
| |
| 1A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.SHEET |
| |
| 1B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS, |
| PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| 90. |
| |
| 1C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |