Plan Review Notes For Permit 19120807 |
Permit Number |
19120807 |
|
Review Stop |
Z |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2020-06-25 13:20:06 | FAILED | | | | 1) REPEAT COMMENT: THE PROPOSED DUCK BANK, WHERE IT | | MEETS THE NORTH SIDE OF THE COOLING TOWER ENCLOSURE, | | APPEARS TO DIRECTLY CONFLICT WITH AN EXISTING SABAL | | PALM TREE. PLEASE REVIEW THE PLACEMENT OF THE DUCT BANK | | TO AVOID THE TREE AND PROVIDE DRAWINGS TO VERIFY THAT | | IT DOES NOT INTERFERE WITH THE EXISTING TREE. ---- NO | | RESPONSE PROVIDED OR CHANGES MADE. | | | | 2) REPEAT COMMENT: ZONING WILL NOT APPROVE THIS PERMIT | | UNTIL A TREE ALTERATION PERMIT HAS BEEN SUBMITTED TO | | THE PLANNING DIVISION AND APPROVED BY THE CITY'S | | LANDSCAPE PLANNER. THIS IS REQUIRED SINCE THE PLANS | | CALL FOR TREES TO BE REMOVED AT THE GENERATOR LOCATION. | | NOTE: THE LATEST PROPOSAL IS TO DESTROY THE TREES. | | PLANNING STAFF IS NOT APPROVING THIS OPTION. THE TREES | | WILL NEED TO BE RELOCATED OR THE GENERATOR INSTALLED IN | | A LOCATION THAT DOES NOT IMPACT THE TREES. | | | | 3) THE FENCE RELOCATION IS APPROVED AS PART OF THIS | | PERMIT AND DOES NOT REQUIRE A SEPARATE FENCE PERMIT. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | [email protected] | | | | |
|