Plan Review Notes
Plan Review Notes For Permit 19120807
Permit Number 19120807
Review Stop Z
Sequence Number 3
Notes
Date Text
2020-06-25 13:20:06FAILED
  
 1) REPEAT COMMENT: THE PROPOSED DUCK BANK, WHERE IT
 MEETS THE NORTH SIDE OF THE COOLING TOWER ENCLOSURE,
 APPEARS TO DIRECTLY CONFLICT WITH AN EXISTING SABAL
 PALM TREE. PLEASE REVIEW THE PLACEMENT OF THE DUCT BANK
 TO AVOID THE TREE AND PROVIDE DRAWINGS TO VERIFY THAT
 IT DOES NOT INTERFERE WITH THE EXISTING TREE. ---- NO
 RESPONSE PROVIDED OR CHANGES MADE.
  
 2) REPEAT COMMENT: ZONING WILL NOT APPROVE THIS PERMIT
 UNTIL A TREE ALTERATION PERMIT HAS BEEN SUBMITTED TO
 THE PLANNING DIVISION AND APPROVED BY THE CITY'S
 LANDSCAPE PLANNER. THIS IS REQUIRED SINCE THE PLANS
 CALL FOR TREES TO BE REMOVED AT THE GENERATOR LOCATION.
 NOTE: THE LATEST PROPOSAL IS TO DESTROY THE TREES.
 PLANNING STAFF IS NOT APPROVING THIS OPTION. THE TREES
 WILL NEED TO BE RELOCATED OR THE GENERATOR INSTALLED IN
 A LOCATION THAT DOES NOT IMPACT THE TREES.
  
 3) THE FENCE RELOCATION IS APPROVED AS PART OF THIS
 PERMIT AND DOES NOT REQUIRE A SEPARATE FENCE PERMIT.
  