Plan Review Notes
Plan Review Notes For Permit 19120807
Permit Number 19120807
Review Stop Z
Sequence Number 2
Notes
Date Text
2020-04-30 16:50:49FAILED
  
 1) THE CIVIL PLAN NEEDS TO SHOW THE FULL EXTENT OF THE
 GENERATOR PAD, INCLUDING DIMENSIONS, IN ITS CORRECT
 LOCATION.
  
 2) THE PROPOSED DUCK BANK, WHERE IT MEETS THE NORTH
 SIDE OF THE COOLING TOWER ENCLOSURE, APPEARS TO
 DIRECTLY CONFLICT WITH AN EXISTING SABAL PALM TREE.
 PLEASE REVIEW THE PLACEMENT OF THE DUCT BANK TO AVOID
 THE TREE AND PROVIDE DRAWINGS TO VERIFY THAT IT DOES
 NOT INTERFERE WITH THE EXISTING TREE.
  
 3) ZONING WILL NOT APPROVE THIS PERMIT UNTIL A TREE
 ALTERATION PERMIT HAS BEEN SUBMITTED TO THE PLANNING
 DIVISION AND APPROVED BY THE CITY'S LANDSCAPE PLANNER.
 THIS IS REQUIRED SINCE THE PLANS CALL FOR TREES TO BE
 REMOVED AT THE GENERATOR LOCATION.
  
 4) THE FENCE RELOCATION IS APPROVED AS PART OF THIS
 PERMIT AND DOES NOT REQUIRE A SEPARATE FENCE PERMIT.
  