Plan Review Notes For Permit 19120807 |
Permit Number |
19120807 |
|
Review Stop |
Z |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2020-04-30 16:50:49 | FAILED | | | | 1) THE CIVIL PLAN NEEDS TO SHOW THE FULL EXTENT OF THE | | GENERATOR PAD, INCLUDING DIMENSIONS, IN ITS CORRECT | | LOCATION. | | | | 2) THE PROPOSED DUCK BANK, WHERE IT MEETS THE NORTH | | SIDE OF THE COOLING TOWER ENCLOSURE, APPEARS TO | | DIRECTLY CONFLICT WITH AN EXISTING SABAL PALM TREE. | | PLEASE REVIEW THE PLACEMENT OF THE DUCT BANK TO AVOID | | THE TREE AND PROVIDE DRAWINGS TO VERIFY THAT IT DOES | | NOT INTERFERE WITH THE EXISTING TREE. | | | | 3) ZONING WILL NOT APPROVE THIS PERMIT UNTIL A TREE | | ALTERATION PERMIT HAS BEEN SUBMITTED TO THE PLANNING | | DIVISION AND APPROVED BY THE CITY'S LANDSCAPE PLANNER. | | THIS IS REQUIRED SINCE THE PLANS CALL FOR TREES TO BE | | REMOVED AT THE GENERATOR LOCATION. | | | | 4) THE FENCE RELOCATION IS APPROVED AS PART OF THIS | | PERMIT AND DOES NOT REQUIRE A SEPARATE FENCE PERMIT. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | [email protected] |
|