2020-04-24 16:33:41GENERATOR ENCLOSURE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) BOTTOM HAND RAIL EXTENSION ON DRAWING 5.3 NEEDS TO
 COMPLY WITH FBC 1014.6 HANDRAIL EXTENSIONS. "CONTINUE
 TO SLOPE FOR THE DEPTH OF ONE TREAD BEYOND THE BOTTOM
 RISER".
 2) GENERATOR HOUSING TIE DOWN (ATTACHMENT TO SLAB)
 NEEDS TO BE A SITE SPECIFIC SIGNED AND SEALED DETAIL
 SHOWING ATTACHMENT TYPE, SIZE, AMOUNT ETC. AND THE WIND
 DESIGN CRITERIA USED FOR DESIGN - FROM AN ARCHITECT OR
 ENGINEER TO COMPLY WITH WIND PRESSURES PER FBC 1609
 (180MPH)
  