Plan Review Notes For Permit 19120807 |
Permit Number |
19120807 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2020-04-24 16:33:41 | GENERATOR ENCLOSURE | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) BOTTOM HAND RAIL EXTENSION ON DRAWING 5.3 NEEDS TO | | COMPLY WITH FBC 1014.6 HANDRAIL EXTENSIONS. "CONTINUE | | TO SLOPE FOR THE DEPTH OF ONE TREAD BEYOND THE BOTTOM | | RISER". | | 2) GENERATOR HOUSING TIE DOWN (ATTACHMENT TO SLAB) | | NEEDS TO BE A SITE SPECIFIC SIGNED AND SEALED DETAIL | | SHOWING ATTACHMENT TYPE, SIZE, AMOUNT ETC. AND THE WIND | | DESIGN CRITERIA USED FOR DESIGN - FROM AN ARCHITECT OR | | ENGINEER TO COMPLY WITH WIND PRESSURES PER FBC 1609 | | (180MPH) | | |
|