2020-04-30 13:47:55 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #19120807 |
| 4/20/2020 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) DESIGN CRITERIA: PROVIDE A LIST OF CODES AND |
| STANDARDS USED IN THE DESIGN OF THE EPSS (EMERGENCY |
| POWER SUPPLY SYSTEM)- SECTION 107.2.1 WPB. |
| |
| 2) PLEASE INDICATE HOW COMPLIANCE IS BEING MET WITH |
| RULE 58A-5.036, F.A.C., EMERGENCY ENVIRONMENTAL CONTROL |
| FOR ASSISTED LIVING FACILITIES. PROVIDE A LIST OF HVAC |
| SYSTEMS TO BE SUPPPORTED BY THE EPSS. |
| |
| 3) REFER TO SECTION 4.1 NFPA 110 AND INDICATE THE LEVEL |
| OF THE EPSS- 1 OR 2, AND SHOW COMPLIANCE WITH 4.4 ITEMS |
| 1, 2, & 3. |
| |
| 4) REFER TO PAGE 6 OF THE SHOP DRAWINGS FOR THE |
| GENERATOR ENCLOSURE WO#46720- 11/27/2019. IT APPEARS |
| THE LOUVER/DAMPER LIST OF PRODUCTS AT THE BOTTOM LEFT |
| OF THE PAGE IS CUT OFF. VERIFY THAT ALL AIR INTAKE AND |
| EXHAUST LOUVERS ARE AMCA 550 RATED IN ACCORDANCE WITH |
| SECTION 401.5 AND 501.3.2 FBC M. |
| |
| 5) MOTORIZED DAMPERS ARE INDICATED IN THE SPECIAL |
| INSTRUCTIONS LIST. PLEASE PROVIDE THE SEQUENCE OF |
| OPERATION FOR THE EXHAUST VENTILATION SYSTEM- SECTION |
| 510.3 AND 510.6.5 FBC M. VERIFY THE DAMPERS ARE IN |
| COMPLIANCE WITH SECTION 7.7.5 NFPA 110. |
| |
| 6) REFER TO SECTION 7.7.4.1 NFPA 110 AND PROVIDE THE |
| STATIC RESTRICTION AT THE RADIATOR DISCHARGE |
| OUTLET.VERIFY THE LOUVERS WILL NOT RESTRICT AIRFLOW. |
| |
| 7) PROVIDE ENGINE EXHAUST PIPING SPECIFICATIONS AND |
| BACKPRESSURE CALCULATIONS- SECTION 7.10.1 NFPA 110 AND |
| SECTION 107.2.1 WPB. |
| |
| 8) PROVIDE THE UL CERTIFICATES FOR THE GENERATOR AND |
| THE FUEL TANK- SECTIONS 304.1 AND 915.1 FBC M. |
| |
| 9) REFER TO SECTIONS 7.13.1 THROUGH 17.13.4.1.6 NFPA |
| 110 AND PROVIDE AN ACCEPTANCE TESTING PROCEDURE |
| OUTLINE. PLEASE NOTE ITEMS #1-4 SECTION 7.13.4.6 SHALL |
| BE MADE AVAILABLE TO THE WPB BUILDING DEPARTMENT FOR |
| FINAL APPROVAL. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |