Plan Review Notes
Plan Review Notes For Permit 19120807
Permit Number 19120807
Review Stop M
Sequence Number 1
Notes
Date Text
2020-04-30 13:47:551ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19120807
 4/20/2020
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) DESIGN CRITERIA: PROVIDE A LIST OF CODES AND
 STANDARDS USED IN THE DESIGN OF THE EPSS (EMERGENCY
 POWER SUPPLY SYSTEM)- SECTION 107.2.1 WPB.
  
 2) PLEASE INDICATE HOW COMPLIANCE IS BEING MET WITH
 RULE 58A-5.036, F.A.C., EMERGENCY ENVIRONMENTAL CONTROL
 FOR ASSISTED LIVING FACILITIES. PROVIDE A LIST OF HVAC
 SYSTEMS TO BE SUPPPORTED BY THE EPSS.
  
 3) REFER TO SECTION 4.1 NFPA 110 AND INDICATE THE LEVEL
 OF THE EPSS- 1 OR 2, AND SHOW COMPLIANCE WITH 4.4 ITEMS
 1, 2, & 3.
  
 4) REFER TO PAGE 6 OF THE SHOP DRAWINGS FOR THE
 GENERATOR ENCLOSURE WO#46720- 11/27/2019. IT APPEARS
 THE LOUVER/DAMPER LIST OF PRODUCTS AT THE BOTTOM LEFT
 OF THE PAGE IS CUT OFF. VERIFY THAT ALL AIR INTAKE AND
 EXHAUST LOUVERS ARE AMCA 550 RATED IN ACCORDANCE WITH
 SECTION 401.5 AND 501.3.2 FBC M.
  
 5) MOTORIZED DAMPERS ARE INDICATED IN THE SPECIAL
 INSTRUCTIONS LIST. PLEASE PROVIDE THE SEQUENCE OF
 OPERATION FOR THE EXHAUST VENTILATION SYSTEM- SECTION
 510.3 AND 510.6.5 FBC M. VERIFY THE DAMPERS ARE IN
 COMPLIANCE WITH SECTION 7.7.5 NFPA 110.
  
 6) REFER TO SECTION 7.7.4.1 NFPA 110 AND PROVIDE THE
 STATIC RESTRICTION AT THE RADIATOR DISCHARGE
 OUTLET.VERIFY THE LOUVERS WILL NOT RESTRICT AIRFLOW.
  
 7) PROVIDE ENGINE EXHAUST PIPING SPECIFICATIONS AND
 BACKPRESSURE CALCULATIONS- SECTION 7.10.1 NFPA 110 AND
 SECTION 107.2.1 WPB.
  
 8) PROVIDE THE UL CERTIFICATES FOR THE GENERATOR AND
 THE FUEL TANK- SECTIONS 304.1 AND 915.1 FBC M.
  
 9) REFER TO SECTIONS 7.13.1 THROUGH 17.13.4.1.6 NFPA
 110 AND PROVIDE AN ACCEPTANCE TESTING PROCEDURE
 OUTLINE. PLEASE NOTE ITEMS #1-4 SECTION 7.13.4.6 SHALL
 BE MADE AVAILABLE TO THE WPB BUILDING DEPARTMENT FOR
 FINAL APPROVAL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  