Plan Review Notes
Plan Review Notes For Permit 19120804
Permit Number 19120804
Review Stop M
Sequence Number 3
Notes
Date Text
2020-06-02 11:34:023RD REVIEW FBC-2017 MECHANICAL
 PERMIT- 19120804
 6/2/2020
  
 CODES IN EFFECT:
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M6.1: THE OUTSIDE AIR CALCULATION SCHEDULE
 INDICATING A BEDROOM, STORAGE ROOM ETC. DOES NOT MATCH
 THE REVISED ARCHITECTURAL FLOOR PLANS AND AREA
 CALCULATIONS- PLEASE CORRECT- TABLE 403.3.1.1 FBC M.
 PLEASE PROVIDE ROOM IDENTIFICATIONS ON THE MECHANICAL
 FLOOR PLANS TO MATCH WITH THE NEW ARCHITECTURAL PLANS-
 SECTION 107.2.1 WPB.
  
 2) AS PREVIOUSLY REQUESTED, PLEASE PROVIDE THE CORRECT
 ADDRESS ON PAGE 2 OF THE ENERGYGAUGE COMPLIANCE REPORT.
 PLEASE NOTE THAT THE ADDRESS ON THE APPLICATION, THE
 PLANS, AND THE ENERGY FORM DO NOT MATCH- SECTION 105.3
 WPB. CORRECT THE 2715 PINEWOOD ADDRESS ON THE FORM TO
 MATCH WITH THE 2723 PINEWOOD ADDRESS ON THE PLANS.
  
 3) COMMENT #4 FROM THE 2ND REVIEW- FAILED. THE $9,500
 JOB VALUE ON THE APPLICATION IS VERY LOW FOR THE SCOPE
 OF THE PROJECT. TOTAL VALUE SHALL INCLUDE THE COSTS OF
 LABOR, MATERIALS, EQUIPMENT, APPLIANCES, FIXTURES ETC.
 FOR ALL TRADES INCLUDING STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE
 WORK, AND SHALL ALSO INCLUDE ARCHITECTURAL AND DESIGN
 FEES, MARKETING COSTS, AND OVERHEAD AND PROFIT.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS- SECTION 109.3 WPB.
  
 THE SUBMITTED COST BREAKDOWN INDICATING $10,000.00 COST
 FOR THE HVAC APPEARS TO BE A VERY LOW VALUE FOR THE NEW
 SYSTEMS AND COMPONENTS BEING INSTALLED AS LISTED BELOW.
 PLEASE PROVIDE A COPY OF THE CONTRACT AND/OR ESTIMATES
 AND INVOICES VERIFYING THE TOTAL COST OF LABOR,
 MATERIALS AND EQUIPMENT FOR THE PROPOSED PROJECT.
  
 A) MITSUBISHI 8-TON VARIABLE REFRIGERANT SYSTEM-
 INCLUDING CU-1 & 2, AND 11 ROOM AIRHANDLERS.
 B) TRANE 4-TON 100% OUTSIDE AIR SYSTEM.
 C) EF- 1 &2 AND EXHAUST DUCTS
 D) GRAVITY VENTILATOR ON THE ROOF
 E) FIRST AND SECOND FLOOR SUPPLY AND RETURN DUCTWORK.
 F) VRF REFRIGERANT LINES
 G) CONDENSATE PIPING.
 H) FIRE DAMPERS, LOUVERS, MOTORIZED DAMPER,
 THERMOSTATS, HUMIDISTATS ETC.
 I) ELECTRONIC CONTROLS FOR THE VRF AND SYSTEMS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  