Date |
Text |
2020-06-02 12:19:20 | PETER E VALENTI |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6673 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| FBC M = FBC MECHANICAL |
| |
| 3RD BUILDING REVIEW DENIED: |
| |
| 1) OK |
| |
| 2) FBC B AND WPB CODE AMENDMENTS 109.3, PLEASE PROVIDE |
| A MORE CLEAR AND DETAILED BREAKDOWN OF COST, INCLUDING |
| THE BREAKDOWN OF ESTIMATES FROM ELEVATOR COMPANY AND |
| ALL OTHER SUBCONTRACTORS ESTIMATES. |
| |
| 3) OK |
| |
| 4) FBC B 508.2.3, THE STORED MATERIAL STILL FALLS UNDER |
| THE GROUPING OF "S-2" AND CONSIDERING THE AREA IS |
| LARGER THANTEN PERCENT OF THE FLOOR AREA, THIS CANNOT |
| BE CONSIDERED AS ACCESSORY OCCUPANCY TO GROUP "B". |
| PLEASE PROVIDE DETAILS ON THE TWO HOUR FIRE RATING |
| BETWEEN OCCUPANCIES. |
| |
| 5) OK |
| |
| 6A) FBC B TABLE 1607.1, PLEASE SHOW THE LIVE LOADS FOR |
| THE SECOND FLOOR STORAGE OCCUPANCY. |
| |
| 6B), 6C), AND 6D) OK |
| |
| 6E) FBC B TABLE 1607.1, 1607.8.1, AND 1609, THE DESIGN |
| PARAMETERS FOR THE STAIRS NEEDS TO BE ON THE PLANS. |
| |
| 7) FBC B 603.1.1.3, ON SHEET A-7 PLEASE PROVIDE A NOTE |
| THAT THE ROOF FRAMING ALONG WITH THE ROOF SHEATHING |
| NEEDS TO BE FIRE RATED. |
| |
| 8) OK |
| 9) OK |
| 10) OK |
| |
| 11) 12) APPROVED WITH PROVISO: FBC B 107.3.4.1, PLEASE |
| PROVIDE THE PRODUCT APPROVALS FOR ALLCOMPONENTS & |
| CLADDING. 2017 FBC?B 1609.1.2 |
| PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| ADMINISTRATIVE CODE 61G20?3.005, RULE 9N?3 NOV. 01/ |
| 2010 (31) SUB?CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS ,MULLIONS |
| (B) WINDOWS & MULLIONS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, ACM PANELS |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| |
| 13) OK |
| |
| 14) APPROVED WITH PROVISO: PLEASE PROVIDE WELDING AND |
| BOLTING DOCUMENTATION IN ACCORDANCE WITH 2017 FBC?B |
| 2204.1 WELDING |
| 2017 FBC?B 2204.2 BOLTING. |
| AWS D1.1 CLAUSE 3.1: AT TIME OF INSPECTION PLEASE |
| PROVIDE A WELD PROCEDURE SPECIFICATION; THE W.P.S. |
| SPECIFIES THE REQUIRED ESSENTIAL VARIABLES INCLUDING: |
| BASE MATERIALS, JOINTS, PROCESS, AND FILLER METALS TO |
| BE USED. |
| AWS D1.1 CLAUSE 4.15: AT TIME OF INSPECTION PLEASE |
| PROVIDE A WELDER PERFORMANCE QUALIFICATION RECORD; THE |
| W.P.Q.R. PROVIDES INFORMATION WHICH CAN BE USED TO |
| VERIFY THE WELDER?S QUALIFICATION AND CERTIFICATION AS |
| IT RELATES TO THE WELDING REQUIREMENTS OF THE PROJECT. |
| |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| |
| |