2020-03-14 08:14:34PLUMBING 2ND REVIEW**DENIED**19120804* YOUR RESPONSE TO
 THESE COMMENTS DID NOT MATCH THE COMMENTS IN CITY
 RECORDS.
  
 1) FBC-PLB 403.1 REQUIRES 2 TOILETS ROOM ON THE 1ST
 FLOOR PER YOUR OCCUPANT LOAD SINCE YOU DO NOT HAVE
 VERTICAL ACCESSIBILITY TO THE 2ND FLOOR TOILET ROOM
 THAT ONE WOULD NOT COUNT TOWARD THE MIN REQUIRED.
 2) UNABLE TO LOCATE THE REQUIRED SERVICE SINK. PLEASE
 ADVISED. FBC-PLB 403.1
 3) THE 2ND FLOOR TOILET SHALL STILL BE REQUIRED PER
 FBC-ACC 213.1. YOU DON NOT SHOW A CLEAR FLOOR SPACE FOR
 THE SHOWER NOR THE TOILET. IT APPEARS YOU ONLY HAVE 44?
 CLEAR FLOOR FOR THE TOILET. PLEASE CLARIFY. FBC 102.1
 4) SHT A4.0 SHOW THE HEIGHT DETAIL TO THE SHOWER VALVE
 AND SHOWER HANDHELD AS MAX 48?. FBC-ACC 608.5.1
  
  
  