Plan Review Notes For Permit 19120804 |
Permit Number |
19120804 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2020-03-14 08:14:34 | PLUMBING 2ND REVIEW**DENIED**19120804* YOUR RESPONSE TO | | THESE COMMENTS DID NOT MATCH THE COMMENTS IN CITY | | RECORDS. | | | | 1) FBC-PLB 403.1 REQUIRES 2 TOILETS ROOM ON THE 1ST | | FLOOR PER YOUR OCCUPANT LOAD SINCE YOU DO NOT HAVE | | VERTICAL ACCESSIBILITY TO THE 2ND FLOOR TOILET ROOM | | THAT ONE WOULD NOT COUNT TOWARD THE MIN REQUIRED. | | 2) UNABLE TO LOCATE THE REQUIRED SERVICE SINK. PLEASE | | ADVISED. FBC-PLB 403.1 | | 3) THE 2ND FLOOR TOILET SHALL STILL BE REQUIRED PER | | FBC-ACC 213.1. YOU DON NOT SHOW A CLEAR FLOOR SPACE FOR | | THE SHOWER NOR THE TOILET. IT APPEARS YOU ONLY HAVE 44? | | CLEAR FLOOR FOR THE TOILET. PLEASE CLARIFY. FBC 102.1 | | 4) SHT A4.0 SHOW THE HEIGHT DETAIL TO THE SHOWER VALVE | | AND SHOWER HANDHELD AS MAX 48?. FBC-ACC 608.5.1 | | | | | | | | TIM HUNT | | PLUMBING PLAN REVIEW | | CITY OF WEST PALM BEACH (CGA SOLUTIONS) | | 561-248-2703 | | [email protected] | | | | | | | | |
|