Date |
Text |
2020-03-11 10:53:12 | 2ND REVIEW FBC-2017 MECHANICAL |
| PERMIT #19120804 |
| 3/11/20 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) M6.1: THE O/A CALCULATION SCHEDULE IS INDICATING 12 |
| SQ. FT. FOR STORAGE WHICH IS NOT CONSISTENT WITH THE |
| FLOOR PLANS AND THE SQUARE FOOTAGE SHOWN IN THE |
| OCCUPANCY CALCS ON SHEET A1.0- TABLE 403.3.1.1. FBC M. |
| |
| 2) M7.1: INDICATE THE TYPE AND SIZE OF ANCHORS FOR |
| ATTACHING THE CONDENSER BRACKETS TO THE SLAB- SECTION |
| 301.15 FBC M. |
| |
| 3) PROVIDE THE CORRECT ADDRESS ON PAGE 2 OF THE |
| ENERGYGAUGE COMPLIANCE REPORT. PLEASE NOTE THAT THE |
| ADDRESS ON THE APPLICATION, THE PLANS, AND THE ENERGY |
| FORM DO NOT MATCH- SECTION 105.3 WPB. |
| |
| 4) THE $9,500 JOB VALUE ON THE APPLICATION IS VERY LOW |
| FOR THE SCOPE OF THE PROJECT. TOTAL VALUE SHALL INCLUDE |
| THE COSTS OF LABOR, MATERIALS, EQUIPMENT, APPLIACES, |
| FIXTURES ETC. FOR ALL TRADES INCLUDING STRUCTURAL, |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| RELATIVE SITE WORK, AND SHALL ALSO INCLUDE |
| ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, AND |
| OVERHEAD AND PROFIT. VALUATION REFERENCES MAY INCLUDE |
| THE LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION COST |
| ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS |
| PUBLISHED BY INTERNATIONAL CODE CONGRESS- SECTION 109.3 |
| WPB. |
| |
| 5) P2.2: SHOW THE OAHU CONDENSATE PIPE AND DISCHARGE |
| LOCATION- SECTION 307.2.1 FBC M. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK ?VOID? OR OLD ON THEM. PLEASE |
| RETAIN THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. |
| THIS PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |
| |