Plan Review Notes
Plan Review Notes For Permit 19120804
Permit Number 19120804
Review Stop B
Sequence Number 2
Notes
Date Text
2020-03-11 15:04:432017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19120804
 ADD: 2719 PINEWOOD AVE. BUILDING C
 CONT: WALKER DESIGN & CONSTRUCTION
 TEL: 561-998-0001
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. MARCH 11/ 2020
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION?S ADDRESS IS NOT THE SAME AS
 THE SUBMITTED PLANS. THE TITLEBLOCK INDICATES THE
 ADDRESS AS 2723 PINEWOOD AVE. BUILDING C (A 2 STORY
 STRUCTURE). THE PERMIT APPLICATION ADDRESS HAS BEEN
 STRUCK AND 2723 PINEWOOD AVE INSERTED. THE CORRECTED
 ADDRESS OF 2723 PINEWOOD THE 2 STORY BUILDING, BUILDING
 C.
  
 2) THE VALUE OF THE PERMIT HAS BEEN INCREASED TO
 $45,000.00 DOLLARS, WHICH IS STILL LOW. SINCE THE
 BUILDING IS GOING TO BE STRUCK DOWN TO THE BLOCK WALLS
 AND A CONCRETE 2ND FLOOR, FLOOR SYSTEM, WE ESTIMATE THE
 VALUE OF THE TYPE II-B AT 50% COST AT 111,864.00 IN
 VALUE FOR 2,400 SQUARE FEET USING THE CURRENT ICC COST
 TABLES.
  
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION 108.3*
 BUILDING PERMIT VALUATION. IF, IN THE OPINION OF THE
 BUILDING OFFICIAL, THE CLAIMED VALUATION OF BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL, OR
 PLUMBING SYSTEMS APPEARS TO BE UNDER ESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 3) NOTE OF INTEREST. SHEET A-1.0. ADDITIONAL
 INFORMATION IS REQUIRED. THERE IS A DISCREPANCY OF
 SQUARE FOOTAGE FOR BUILDING # 2 ( C ) WITH THE PALM
 BEACH COUNTY PROPERTY APPRAISERS OFFICE, AND WITH THE
 CITY RECORDS (GREEN CARDS) AND THE WORK SHOWN IN THESE
 DRAWINGS. IT WOULD APPEAR THAT YOU ARE PAYING FOR AN
 ADDITIONAL 1,600 SQ. FT. ON TAXES THAT IS NOT THERE.
 PALM BEACH COUNTY HAS THE TOTAL SQUARE FOOTAGE AT 4,000
 SQ. FT. THE CITY RECORDS (GREEN CARDS) MATCH THE
 EXISTING FOOTPRINT OF THE EXISTING BUILDING. THE 1ST
 FLOOR 1,500 SQ. FT. THE 2ND FLOOR OLD APARTMENT 900 SQ.
 FT. FOR A TOTAL OF 2,400 SQ. FT.
 SHEET A1.0 DETAIL # 2INDICATES 1ST FLOOR AS 1,500 SQ.
 FT. AND THE 2ND FLOOR AS 900 SQ. FT. FOR A TOTAL OF
 2,400 SQ. FT. WHEN YOU LOOK AT DETAIL # 7 THE SQUARE
 FOOTAGE FOR THE 1ST FLOOR AND 2ND FLOOR TOTALS TO 3,755
 SQUARE FEET, A LOT CLOSER TO THE P.B. COUNTY PROPERTY
 APPRAISERS FIGURE OF 4,000 SQ. FT. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 4) 2ND REQUEST. SEMI-COMPLIED. THE TITLE SHEET, A-1.0
 INDICATES THE PRIMARY OCCUPANCY AS S2 ORDINARY HAZARD
 STORAGE AND BUSINESS OCCUPANCY. THE PLAN INDICATES A 2
 HOUR SEPARATION BETWEEN THE S2 AND BUSINESS
 OCCUPANCIES. THEN TAKES AN EXCEPTION LISTING 508.2.4.
 PLEASE REVIEW SECTION 508.2 OF THE 2017 FBC-B.
 ACCESSORY OCCUPANCIES MUST COMPLY WITH THE PROVISIONS
 OF SECTIONS 508.2.1 THROUGH 508.2.4.PLEASE REVIEW
 508.2.3. AGGREGATE ACCESSORY OCCUPANCIES SHALL NOT
 COVER MORE THAN 10% OF THE FLOOR AREA OF THE STORY IN
 WHICH THEY ARE LOCATED. 935/ 2468= 0.378 % OF THE FLOOR
 AREA OVER 0.10%.
 TABLE 508.4 WILL REQUIRE A 2 HOUR FIRE RATING BETWEEN
 THE S2 AND BUSINESS OCCUPANCY.
  
 5) 2ND REQUEST. THE TITLE SHEET, SHEET A-1.0 LIST THE
 CLASSIFICATION OF WORK AS A LEVEL 3 ALTERATION. THE
 LAST KNOWN USE FOR THE 2ND STORY IS AN APARTMENT, WHICH
 WOULD CONSTITUTE A CHANGE OF OCCUPANCY FOR THE UPSTAIRS
 AND COMPLIANCE WITH THE 2017 FBC-EXISTING BUILDING CODE
 SECTION 1001.2.2.1 PARTIAL CHANGE OF OCCUPANCY, PLEASE
 UPDATE THE PLANS.
  
 6A) 2ND REQUEST. THE TITLE SHEET NOR A-1.1 CODES &
 SPECS PROVIDE THE LIVE LOADS THE 2ND FLOOR WAS DESIGNED
 FOR? THE STORAGE OCCUPANCY OF THE 2ND FLOOR DOES NOT
 STATE THE LIVE LOADS TO BE IMPOSED, PLEASE SHOW
 COMPLIANCE WITH 2017 FBC-B TABLE 1607.1(31).
  
 6B) 2ND REQUEST. 2017 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATIVE CODE
 SECTION 106.1 LIVE LOADS POSTED. WHERE THE LIVE LOADS
 FOR WHICH EACH FLOOR OR PORTION THEREOF OF A COMMERCIAL
 OR INDUSTRIAL BUILDING IS OR HAS BEEN DESIGNED TO
 EXCEED 50 PSF, SUCH DESIGN LIVE LOADS SHALL BE
 CONSPICUOUSLY POSTED BY THE OWNER IN THAT PART OF EACH
 STORY IN WHICH THEY APPLY, USING DURABLE SIGNS. IT
 SHALL BE UNLAWFUL TO REMOVE OR DEFACE SUCH NOTICES?
  
 6C) 2ND REQUEST. 2017 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1OF THE ADMINISTRATIVE
 CODE SECTION 106.2 ISSUANCE OF CERTIFICATE OF
 OCCUPANCY. A CERTIFICATE OF OCCUPANCY REQUIRED BY
 SECTION 111 SHALL NOT BE ISSUED UNTIL THE FLOOR LOAD
 SIGNS, REQUIRED BY SECTION 106.1, HAVE BEEN INSTALLED.
  
 6D)2ND REQUEST. 2017 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1 OF THE ADMINISTRATIVE
 CODE SECTION 106.3 RESTRICTIONS ON LOADING. IT SHALL BE
 UNLAWFUL TO PLACE, OR CAUSE OR PERMIT TO BE PLACED, ON
 ANY FLOOR OR ROOF OF A BUILDING, STRUCTURE OR PORTION
 THEREOF, A LOAD GREATER THAN IS PERMITTED BY THIS CODE.
 PLEASE PROVIDE CALCULATIONS FOR THE ALLOWABLE LOADS TO
 BE POSTED.
  
 6E) 2ND REQUEST. THE TITLE SHEET UNDER THE SCOPE OF
 WORK STATES ON THE EXTERIOR OF THE BUILDING (REAR/ WEST
 SIDE) A NEW METAL STAIRWAY AND STEEL COLUMNS ARE TO BE
 DESIGNED BY A DELEGATE ENGINEER. THE DESIGN
 PROFESSIONAL HAS NOT PROVIDED DESIGN PARAMETERS FOR THE
 STAIR (FBC-B TABLE 1607.1(30). THERE IS NO DESIGN
 PERIMETERS FOR THE HANDRAIL OR GUARDRAIL SYSTEMS, FBC-B
 1607.8.1, 1609, WIND.
  
 7) 2ND REQUEST. SHEET A1.1 CODES AND SPECS UNDER THE
 HEADING OF FIRE RESISTANCE RATING REQUIREMENT DETAIL 4
 FOR BUILDING ELEMENTS TABLE 601- FOR TYPE: V-B
 CONSTRUCTION. UNDER THE HEADING # 2 PROJECT INFORMATION
 THE CONSTRUCTION TYPE IS LISTED AS CONSTRUCTION TYPE
 II-B. PLEASE CORRECT CONSTRUCTION TYPE, THE PLANS HAVE
 TO BE DESIGNED TO THE SAME CONSTRUCTION TYPE. YOU HAVE
 INDICATED THROUGHOUT THE PLANS (A-6.0) THE ROOF
 SHEATHING HAS TO BE FIRE RETARDANT TREATED WOOD,
 CONSISTENT WITH CONSTRUCTION TYPE II-B CONSTRUCTION.
 SHEET A-6.0 DOES NOT STATE THE REMOVAL OF THE EXISTING
 ROOF JOIST AND REPLACEMENT WITH FIRE-RESISTANT TREATED
 WOOD AS REQUIRED BY THE 2017 FBC-B SECTION 603.1.1.3.
 SHEET A-7.0 INDICATES A NEW PRE-ENGINEERED GALVALUME
 MR-24 STANDING SEAM ROOF OVER PRE-EXISTING ROOF. NO
 MENTION AS TO THE FIRE RETARDANT TREATED ROOF FRAMING
 MEMBERS AND FIRE RETARDANT TREATED ROOF SHEATHING.
  
 8A) 2ND REQUEST. SHEET A4.4. WHEN THERE IS ONLY ONE
 MEANS OF EGRESS YOU TAKE THE DISTANCE OUT OF THE EXIT
 DOOR AND DOWN THE STAIRS TO THE 1ST FLOOR LANDING. IT
 APPEARS THE 2ND FLOOR OCCUPANCY ONLY HAVING ONE MEANS
 OF EGRESS IS OVER THE COMMON PATH OF TRAVEL FOR STORIES
 WITH ONE EXIT OR ACCESS TO ONE EXIT FOR OTHER
 OCCUPANCIES SEE THE 2017 FBC-B TABLE 1006.3.2(2). FOR
 STORAGE OCCUPANCIES THE COMMON PATH OF TRAVEL IS
 LIMITED TO 75 FEET. THE COMMON PATH OF TRAVEL IS
 MEASURED FROM THE FURTHEST POINT ON THE ROOF DECK
 THROUGH THE 2ND FLOOR AND DOWN THE STAIRS TO THE BOTTOM
 LANDING THAT IS WHERE YOU HAVE A CHOICE OF DIRECTION TO
 THE PUBLIC WAY.
  
 8B-G) COMPLIED.
  
 9-10) COMPLIED.
  
 11) COMPONENTS & CLADDING. 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS, ACM PANELS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 11A-C) COMPLIED.
  
 12A-G) PROVISO: ACM PANELS NOA: 18-0725.15 SHOP
 DRAWINGS FOR THIS SYSTEM WILL BE SUBMITTED BY THE
 DELEGATE CONTRACTOR TO THE ARCHITECT FOR REVIEW AND
 APPROVAL.
  
 12H) ROOF PRODUCT APPROVAL NOA 19-0708.07 SHOP DRAWINGS
 FOR THIS SYSTEM WILL BE SUBMITTED BY THE DELEGATE
 CONTRACTOR TO THE ARCHITECT FOR REVIEW AND APPROVAL.
  
 13) A-4.0 2017 FBC-ACCESSIBILITY CODE: .
 13A-B) COMPLIED.
  
 13C)(1) THE LIFE SAFETY PLAN AND A-4.0 SHOW THE HIGH/
 LOW DRINKING FOUNTAINS. PLEASE SHOW COMPLIANCE WITH THE
 2017 FBC-ACCESSIBILITY CODE SECTION 211.2 MINIMUM
 NUMBER. NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE
 PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1
 THROUGH 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY
 WITH 602.7.
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
  
 13C)(2) DEPENDING ON THE LOCATION OF THE DRINKING
 FOUNTAINS THE NEED TO SHOW COMPLIANCE WITH THE 2017
 FBC-ACCESSIBILITY CODE SECTION 602.1 DRINKING FOUNTAINS
 SHALL COMPLY WITH 307. PROTRUDING OBJECTS.
  
 13D) DETAIL # 5 MAKES REFERENCES TO FACBC 11.4 THIS
 REFERENCE IS NOT TO THE CURRENT CODE SECTIONS. UNDER
 THE 2017 FBC-ACCESSIBILITY CODE THERE IS NO CHAPTER 11.
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 14) BUILDING PROVISO: SHEETS A-6.0 AND S-3.0 BOTH SHOW
 THE INSTALLATION OF STRUCTURAL STEEL FRAMING MEMBERS
 AND ANCHORING OF ROOF FRAMING INTO THE TWIN TEE ROOF
 FRAMING. WHEN THERE IS EITHER WELDING OR BOLTING OF
 STRUCTURAL MEMBERS THEN THE CONTRACTOR IS REQUIRED TO
 PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR
 PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH
 THE REFERENCED STANDARDS AT TIME OF INSPECTION. IN
 ACCORDANCE WITH THE AMERICAN WELDING SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
 THE CONTRACTOR WOULD NEED TO GET A 3RD PARTY ENGINEER
 TO PROVIDE INSPECTIONS. CURRENTLY THERE ARE NO SHOP
 DRAWING SUBMITTED, CONNECTION TYPE ARE UNKNOWN.
 IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS
 FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU.
  
 15) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  