2020-01-29 16:39:42 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #19120804 |
| 1/29/20 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEETS A1.0, A4.0, M2-1, M2-2: THE ROOM |
| IDENTIFICATIONS ON THE MECHANICAL PLANS DO NOT MATCH |
| THE ARCHITECTURAL PLANS. THE MECHANICAL PLANS INDICATE |
| THE 2ND FLOOR IS PARTIALLY A RESIDENTIAL OCCUPANCY. THE |
| DESIGN PROFESSIONALS MATCHING PLANS AND CORRECT |
| OCCUPANCY CLASSIFCATIONS- SECTION 107.2.1 WPB. |
| |
| 2) M6.1: PLEASE PROVIDE VENTILATION CALCULATIONS PER |
| OCCUPANCY CLASSIFICATIONS AS OUTLINED IN TABLE |
| 403.3.1.1 FBC M. |
| |
| 3) M2.2: FIRE DAMPERS MAY BE REQUIRED AT THE O/A DUCT |
| PENETRATIONS OF THE FLOOR/CEILING ASSEMBLY- SEE SECTION |
| 607.6. THE SHAFT CONTAINING THE O/A DUCT DROPS DOES NOT |
| APPEAR TO BE FIRE-RATED, HOWEVER A FIRE-RATED |
| FLOOR/CEILING ASSEMBLY MAY BE REQUIRED FOR SEPARATION |
| OF THE S, R, & B OCCUPANCIES. |
| |
| 4) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF |
| THE AC CONDENSER UNITS AND ROOFTOP GRAVITY VENTILATOR- |
| SECTION 301.15 FBC M. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK ?VOID? OR ?OLD? ON THEM. PLEASE |
| RETAIN THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. |
| THIS PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |