Plan Review Notes
Plan Review Notes For Permit 19120804
Permit Number 19120804
Review Stop M
Sequence Number 1
Notes
Date Text
2020-01-29 16:39:421ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19120804
 1/29/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A1.0, A4.0, M2-1, M2-2: THE ROOM
 IDENTIFICATIONS ON THE MECHANICAL PLANS DO NOT MATCH
 THE ARCHITECTURAL PLANS. THE MECHANICAL PLANS INDICATE
 THE 2ND FLOOR IS PARTIALLY A RESIDENTIAL OCCUPANCY. THE
 DESIGN PROFESSIONALS MATCHING PLANS AND CORRECT
 OCCUPANCY CLASSIFCATIONS- SECTION 107.2.1 WPB.
  
 2) M6.1: PLEASE PROVIDE VENTILATION CALCULATIONS PER
 OCCUPANCY CLASSIFICATIONS AS OUTLINED IN TABLE
 403.3.1.1 FBC M.
  
 3) M2.2: FIRE DAMPERS MAY BE REQUIRED AT THE O/A DUCT
 PENETRATIONS OF THE FLOOR/CEILING ASSEMBLY- SEE SECTION
 607.6. THE SHAFT CONTAINING THE O/A DUCT DROPS DOES NOT
 APPEAR TO BE FIRE-RATED, HOWEVER A FIRE-RATED
 FLOOR/CEILING ASSEMBLY MAY BE REQUIRED FOR SEPARATION
 OF THE S, R, & B OCCUPANCIES.
  
 4) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF
 THE AC CONDENSER UNITS AND ROOFTOP GRAVITY VENTILATOR-
 SECTION 301.15 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK ?VOID? OR ?OLD? ON THEM. PLEASE
 RETAIN THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS.
 THIS PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  