Date |
Text |
2020-01-07 11:37:41 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| NFPA 54 = NATIONAL FUEL GAS CODE |
| NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| NFPA 99 = HEALTH CARE FACILITIES CODE |
| NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| |
| 1ST REVIEW |
| |
| PLUMBING COMMENTS: DENIED |
| |
| 1. PLAN SHEET A-1: SCOPE OF WORK; NOTE 8 CALLS FOR |
| REMOVAL OF BATHTUBS AND REPLACE WITH SHOWERS. THIS IS |
| REINFORCED BY THE ENLARGED FLOOR PLANS AND ELEVATION |
| PLANS ON PLAN SHEET A-3. PLAN SHEETS A-1, E-1, P-1, P-2 |
| AND P-3 INDICATE SOME UNITS WITH SHOWERS AND SOME WITH |
| BATHTUBS. PER WPB FBC 107.2.1, CLARIFY AND RECONCILE |
| ALL PLANS. |
| 2. PER WPB FBC 107.2.1, PROVIDE ASSEMBLIES COMPLYING |
| WITH FBC CHAPTER 7, FOR ANY PIPE PENETRATIONS THROUGH |
| FIRE RATED FLOORS AND WALLS. |
| 3. PLAN SHEET P-2: SELECTED WATER HEATER PROVIDES A |
| MAXIMUM OF 2.7 GPM. THIS APPEARS NOT TO SATISFY THE |
| REQUIREMENTS FOR HOT WATER FOR THE FIXTURES REQUIRING |
| HOT WATER. PER WPB FBC 107.2.1, PROVIDE CALCULATIONS |
| FOR THE HOT WATER DEMAND AND SELECT A WATER HEATER |
| BASED ON THE CALCULATIONS THAT WILL SATISFY THE HOT |
| WATER REQUIREMENTS. PROVIDE MANUFACTURER'S |
| SPECIFICATION FOR SAID WATER HEATER. PROVIDE LOCATION |
| ON PLAN FOR THE UNIT WHICH IS ACCESSIBLE AS REQUIRED BY |
| FBC PL 501.4. |
| 4. PER WPB FBC 107.2.1, PROVIDE PLUMBING FIXTIURE |
| SCHEDULE INDICATING TYPE, WATER DEMAND/WATER SUPPLY |
| SIZE, SANITARY FIXTURE UNIT LOAD/TRAP SIZE |
| 5. PER WPB FBC 107.2.1, PROVIDE NOTE "SHUT OFF VALVES |
| FOR WASHER/ DRYER COMBO SHALL BE ACCESSIBLE PER FBC PL |
| 606.3". |
| 6. PLAN SHEET P-1 PLAN VIEW AND P-3 SANITARY RISERS; |
| FIXTURE DRAIN FOR WASHER IS NOTED AS 3 INCH SIZE. PER |
| FBC 2308.5.10, THIS IS PROHIBITED. FIXTURE DRAIN AND |
| TRAP SHALL BE SIZED 2 INCH IN ACCORDANCE WITH THE |
| MINIMUM REQUIREMENTS OF FBC PL 709.1. |
| 7. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE ON THE |
| SANITARY RISER DIAGRAMS THE EXISTING UNDERGROUND |
| DRAINAGE AND VENTING SO THAT A COMPREHENSIVE REVIEW OF |
| THE PROJECT CAN BE COMPLETED. I NOTE THAT UNIT 6 AND |
| UNIT 7 ARE DISCHARGING INTO THE VENT STACK AND THROUGH |
| THE VENT FOR THE GROUND FLOOR FIXTURES WHICH IS |
| PROHIBITED. ADDITIONALLY, I NOTE THAT THERE IS NO VENT |
| STACK SHOWN FOR UNITS 1/5 AND 4/8 WHICH IS A |
| REQUIREMENT. WHEN ADDRESSING ALSO NOTE THAT PER FBC PL |
| 912.2 THAT ONLY BATHROOM GROUP FIXTURES AS DEFINED IN |
| FBC PL CHAPTER 2 MAY CONNECT TO THE WET VENT AND ONLY |
| ON THE SAME FLOOR. |
| 8. VALUE OF WORK APPEARS TO BE LOW. PER WPB FBC 109.3, |
| PROVIDE DETAILED QUANTITY ESTIMATES AND/OR BONA FIDE |
| SIGNED CONTRACTS TO MEET THE BUILDING OFFICIALS |
| APPROVAL. VALUATION SHALL BE FOR THE TOTAL REPLACEMENT |
| VALUE OF STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, |
| INTERIOR FINISHES, RELATIVE SITE WORK, ARCHITECTURAL |
| AND DESIGN FEES. |
| |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-805-6715 |
| |
| 19120794 710 10TH ST |
| |
| |
| |