Plan Review Notes
Plan Review Notes For Permit 19120794
Permit Number 19120794
Review Stop M
Sequence Number 1
Notes
Date Text
2020-01-15 14:30:04 
 1ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19120794
 1/15/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) NO MECHANICAL PLANS HAVE BEEN SUBMITTED. PLEASE
 CLARIFY IF ANY ALTERATIONS TO THE EXISTING HVAC SYSTEMS
 ARE PROPOSED INCLUDING KITCHEN AND BATTH EXHAUST
 SYSTEMS, AC SYSTEM REPLACEMENTS, OR DUCT ALTETRATIONS-
 SECTION 107.2.1 WPB. PLEASE NOTE THAT MECHANICAL
 EXHAUST IS REQUIRED FOR THE BATHS AT AN INTERMITTENT
 RATE OF 50 CFMS, AND FOR THE KITCHENS AT AN
 INTERMITTENT RATE OF 100 CFMS- TABLE 403.3.1.1 FBC M.
  
 2) SUBMIT PRODUCT DATA SHEETS FOR ALL NEW KITCHEN
 APPLIANCES AND EXHAUST SYSTEMS- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved