2020-01-23 13:43:55PLUMBING COMMENTS: APPROVED WITH PROVISO
 PUMP DISCHARGE SHALL NOT CONNECT TO THE FLOOR SINK
 FIXTURE DRAIN IN THE KITCHEN. PER FBC PL 712.3.5, PUMPS
 CONNECTED TO THE DRAINAGE SYSTEM SHALL CONNECT TO A
 BUILDING SEWER, BUILDING DRAIN, SOIL STACK, WASTE STACK
 OR HORIZONTAL BRANCH DRAIN. WHERE THE DISCHARGE LINE
 CONNECTS INTO HORIZONTAL DRAINAGE PIPING, THE
 CONNECTION SHALL BE MADE THROUGH A WYE FITTING INTO THE
 TOP OF THE DRAINAGE PIPING AND SUCH WYE FITTING SHALL
 BE LOCATED NOT LESS THAN 10 PIPE DIAMETERS FROM THE
 BASE OF ANY SOIL STACK, WASTE STACK OR FIXTURE DRAIN.
  