2020-01-23 13:43:55 | PLUMBING COMMENTS: APPROVED WITH PROVISO | | PUMP DISCHARGE SHALL NOT CONNECT TO THE FLOOR SINK | | FIXTURE DRAIN IN THE KITCHEN. PER FBC PL 712.3.5, PUMPS | | CONNECTED TO THE DRAINAGE SYSTEM SHALL CONNECT TO A | | BUILDING SEWER, BUILDING DRAIN, SOIL STACK, WASTE STACK | | OR HORIZONTAL BRANCH DRAIN. WHERE THE DISCHARGE LINE | | CONNECTS INTO HORIZONTAL DRAINAGE PIPING, THE | | CONNECTION SHALL BE MADE THROUGH A WYE FITTING INTO THE | | TOP OF THE DRAINAGE PIPING AND SUCH WYE FITTING SHALL | | BE LOCATED NOT LESS THAN 10 PIPE DIAMETERS FROM THE | | BASE OF ANY SOIL STACK, WASTE STACK OR FIXTURE DRAIN. | | |
|