Plan Review Notes
Plan Review Notes For Permit 19120743
Permit Number 19120743
Review Stop P
Sequence Number 1
Notes
Date Text
2020-01-06 10:38:501) SUBMIT AN EXISTING AND PROPOSED FLOOR PLAN FOR
 REVIEW. WPB AMEND. TO FBC SEC. 107.2.1.
 2) SUBMIT A WATER RISER FOR REVIEW. WPB AMEND. TO FBC
 SEC. 107.3.5.1.3.
 3) SUBMIT A COPY OF THE MANUFACTURER'S SPECIFICATIONS
 FOR THE POINT OF USE WATER HEATER.WPB AMEND. TP FBC
 SEC. 107.2.1.
 4) THERE IS A NOTE BY THE VENT FOR THE HANDSINK THAT
 READS "PUMPED 2" TO FLOOR SINK IN KITCHEN". CLARIFY.
 5) IDENTIFY ALL INDIRECT WASTES ON THE SANITARY RISER.
 6) SHT. 3.0P SHOWS 2 FLOOR SINKS ON THE SANITARY RISER
 BUT THE FLOOR PLAN SHOWS 3. CLARIFY.
 7) SIZE THE VENT FOR THE HAND SINK. COMPLY WITH 2017
 FBC-PLUMBING SEC.906.1.
 8) SUBMIT COMPLETE SPECIFICATIONS FOR THE LIBERTY SUMP
 AND PUMP. THE SUMP SHALL COMPLY WITH 2017 FBC-PLUMBING
 SEC.712.3.2.
 9) SIZE THE VENT FOR THE SUMP/PUMP. COMPLY WITH
 MANUFACTURER'S INSTALLATION MANUAL.
 9) THE PUMP CANNOT BE INDIRECTLY WASTED AS SHOWN. THE
 EJECTOR SHALL CONNECT TO THE DRAINAGE SYSTEM IN
 ACCORDANCE WITH 2017 FBC-PLUMBING SEC.712.3.5.
 10) A CHECK VALVE AND A FULL OPEN GATE VALVE ARE
 REQUIRED IN THE PUMP EJECTOR DISCHARGE PIPING PER 2017
 FBC-PLUMBING SEC.712.2.
  