Plan Review Notes For Permit 19120743 |
Permit Number |
19120743 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-01-06 10:38:50 | 1) SUBMIT AN EXISTING AND PROPOSED FLOOR PLAN FOR | | REVIEW. WPB AMEND. TO FBC SEC. 107.2.1. | | 2) SUBMIT A WATER RISER FOR REVIEW. WPB AMEND. TO FBC | | SEC. 107.3.5.1.3. | | 3) SUBMIT A COPY OF THE MANUFACTURER'S SPECIFICATIONS | | FOR THE POINT OF USE WATER HEATER.WPB AMEND. TP FBC | | SEC. 107.2.1. | | 4) THERE IS A NOTE BY THE VENT FOR THE HANDSINK THAT | | READS "PUMPED 2" TO FLOOR SINK IN KITCHEN". CLARIFY. | | 5) IDENTIFY ALL INDIRECT WASTES ON THE SANITARY RISER. | | 6) SHT. 3.0P SHOWS 2 FLOOR SINKS ON THE SANITARY RISER | | BUT THE FLOOR PLAN SHOWS 3. CLARIFY. | | 7) SIZE THE VENT FOR THE HAND SINK. COMPLY WITH 2017 | | FBC-PLUMBING SEC.906.1. | | 8) SUBMIT COMPLETE SPECIFICATIONS FOR THE LIBERTY SUMP | | AND PUMP. THE SUMP SHALL COMPLY WITH 2017 FBC-PLUMBING | | SEC.712.3.2. | | 9) SIZE THE VENT FOR THE SUMP/PUMP. COMPLY WITH | | MANUFACTURER'S INSTALLATION MANUAL. | | 9) THE PUMP CANNOT BE INDIRECTLY WASTED AS SHOWN. THE | | EJECTOR SHALL CONNECT TO THE DRAINAGE SYSTEM IN | | ACCORDANCE WITH 2017 FBC-PLUMBING SEC.712.3.5. | | 10) A CHECK VALVE AND A FULL OPEN GATE VALVE ARE | | REQUIRED IN THE PUMP EJECTOR DISCHARGE PIPING PER 2017 | | FBC-PLUMBING SEC.712.2. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | |
|