| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. ELECTRICAL PLANS ARE MISSING A LOT OF INFORMATION, A |
| COMPLETE REVIEW IS NOT POSSIBLE AT THIS TIME. PROVIDE |
| LEGEND OF SYMBOLS USED ON PLAN. SHOW ALL RECEPTACLE AND |
| LIGHTING SWITCHES AND OUTLETS ON PLAN. PROVIDE LIGHT |
| FIXTURE SCHEDULE AND INDICATE FIXTURE TYPES ON PLAN. |
| WPB FBC 107.2.1 |
| 2. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE, |
| INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF |
| SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| |