2020-02-06 13:53:13 | THESE GAS PLANS WERE ORIGINALLY REVIEWED UNDER PERMIT |
| #19120638. |
| |
| 1) THE GAS LANTERNS SHALL BE LISTED AND LABELED PER |
| 2017 FBC-RESIDENTIAL SEC. G2404.3.SUBMIT MANUFACTURER |
| SPECIFICATIONS THAT SHOW THE UNITS COMPLY.THERE IS NO |
| INFORMATION ON THE SUBMITTED DOCUMENTS THAT SHOW THAT |
| THESE LANTERNS ARE LISTED AND LABELED. |
| 2) ) INSTALLATIONS WITHIN 10 FT (3 M) OF A PUBLIC |
| VEHICULAR THOROUGHFARE OR DESIGNATED PARKING LOCATION |
| SHALL BE PROVIDED WITH VEHICULAR BARRIER PROTECTION FOR |
| THE CONTAINER'S FITTING HOUSING, HOUSING COVER, |
| CONTAINER CONNECTIONS, AND PIPING. NFPA 58-14 SEC. |
| 6.6.6.1 (C).SHOW HOW THE LP TANK WILL BE PROTECTED FROM |
| DAMAGE . |
| 3) SHOW THE DISTANCE OF THE LP TANK FROM THE EDGE OF |
| THE DRIVEWAY ON THE SURVEY. WPB AMEND. TO FBC SEC. |
| 107.2.1. |
| 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE GRILL. |
| THE GRILL SHALL BE LISTED AND LABELED. 2017 |
| FBC-RESIDENTIAL SEC. G2404.3. |
| 5) WHERE CONNECTED TO RIDGID PIPING, A UNION SHALL BE |
| INSTALLED WITHIN 1 FOOT OF EITHER SIDE OF THE MP |
| REGULATOR. 2017 FBC-RES. SEC. G2421.2 (7). NOTE THIS ON |
| THE GAS RISER DRAWING. |
| 6) THE SUBMITTED SHEET FOR THE CATHODIC PROTECTION IS A |
| POOR COPY AND SOME AREAS ARE ILLEGIBLE. SUBMIT TWO |
| CLEAR AND LEGIBLE COPIES. WPB AMEND. TO FBC SEC. |
| 107.2.1. |
| 7) TWO DIFFERENT SIZING TABLES HAVE BEEN SUBMITTED FOR |
| THE HIGH PRESSURE POLYETHYLENE PIPE.ONE TABLE DOESN'T |
| HAVE A COLUMN FOR 3/4 INCH PIPE. CLARIFY. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |