Plan Review Notes For Permit 19120626 |
Permit Number |
19120626 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-12-18 12:59:58 | DISCUSSED WITH KEN CONRAD, CHIEF INSPECTOR. FROM THE | | PHOTOS THAT WERE SUBMITTED, IT APPEARS THAT THE 4'X4' | | INSULATION BOARD WAS ATTACHED TO THE WOOD DECK WITH 4 | | FASTENERS. THE PRODUCT APPROVAL THAT WAS APPROVED BY | | THE CITY REQUIRES ONE FASTENER PER SQUARE FOOT WHICH IS | | 16 FASTENERS FOR A 4'X4' (16 SQFT) ISO BOARD. GAVE ALL | | DOCUMENTS TO K.CONRAD TO MEET WITH CONTRACTOR TO | | RESOLVE THE ISSUE. |
|