2020-05-18 12:28:07 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE RESPONSE LETTER STATES THAT THE DISTANCE FROM | | THE NORTH WALL OF THE FULLY SPRINKLERED BUILDING TO THE | | CENTER LINE OF THE ALLEY IS 7'-2". BY THE DEFINITION IN | | FBC SECTION 202, THIS IS THE FIRE SEPARATION DISTANCE. | | FOR A FIRE SEPARATION DISTANCE OF 5 FEET TO LESS THAN | | 10 FEET FOR A FULLY SPRINKLERED BUILDING, FBC TABLE | | 705.8 LISTS THE AREA OF ALLOWABLE OPENINGS AS 25 | | PERCENT OF THE WALL AREA PER STOREY. ITEM #6 OF THE | | RESPONSE LETTER AND SHEET A-2 OF THE PLANS HAVE THE | | ALLOWABLE AREA AS 45 PERCENT. PLEASE CORRECT. | | | | 2) THE PROPOSED GLAZING ANALYSIS ON SHEET A-2, | | SPECIFIES THE TOTAL OF NEW GLAZING AND DOES NOT INCLUDE | | EXISTING OPENINGS. WHEN DETERMINING TO PERCENTAGE OF | | ALLOWABLE OPENINGS FOR STOREY OF A BUILDING, YOU ARE | | REQUIRED TO INCLUDE ALL OPENINGS (NEW AND EXISTING), | | EVEN THOSE THAT DON'T HAVE GLAZING. FBC 705.8 | | | | 3) IN ORDER TO SPEED YOUR PLAN REVIEW, IT IS HELPFUL TO | | PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM. |
|