2020-01-06 19:01:34 | PLAN REVIEW COMMENTS FOR REVISION #19120609 |
| |
| 1ST REVIEW: FBC SIXTH EDITION (2017) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THE ONE REVISED PLAN SHEET LABELED "GROUND |
| FLOOR/REFLECTED CEILING PLAN" THAT SHOWS THE RECESSED |
| LIGHTS AND STUCCO REPAIR IS OKAY, OTHER THAN IT HAS THE |
| SAME DRAWING NUMBER "A-1" AS THE PROPOSED FLOOR PLANS |
| FOR THE GROUND AND UPPER LEVEL. A REFLECTED CEILING |
| PLAN HAD NOT BEEN SUBMITTED PREVIOUSLY. PLEASE ASSIGN A |
| NEW DRAWING NUMBER TO THIS DRAWING TO SHOW THAT IT IS |
| NOT REVISING PREVIOUSLY SUBMITTED DRAWINGS. FBC |
| 107.2.1.3 |
| |
| 2) IN ADDITION TO THE ONE NEW SHEET, THREE OTHER SHEETS |
| WERE SUBMITTED. THE FEES THAT WERE CHARGED ARE FOR ONLY |
| A ONE PAGE REVISION. DURING MY REVIEW I DISCOVERED |
| THERE WAS SOME REQUIRED ITEMS MISSING FROM THE APPROVED |
| PLANS AND THAT THE WINDOWS SHOWN ON THE BUILDING'S |
| NORTH ELEVATION ON SHEET A-2 DIFFER FROM THE APPROVED |
| PLANS. THIS WILL REQUIRE A REVISION. FBC 107.2.1 |
| |
| 3) I DID NOT SEE A WINDOW SCHEDULE ON THE APPROVED |
| PLANS. PLEASE SUBMIT A WINDOW SCHEDULE THAT SHOWS THE |
| TYPE AND SIZE OF THE WINDOWS THAT WILL BE INSTALLED. |
| FBC 107.2.1.2 |
| |
| 4) A REVISED STRUCTURAL PLAN THAT SPECIFIES THE |
| REQUIRED DESIGN PRESSURES FOR EACH OF THE WINDOWS AND |
| EXTERIOR DOORS IS REQUIRED. FBC 107.2.1 |
| |
| 5) PRODUCT APPROVALS AND SHOP DRAWINGS FOR THE STORE |
| FRONT WINDOWS AND EXTERIOR DOORS ARE REQUIRED TO BE |
| SUBMITTED. THIS CAN BE DONE AS A DEFERRED SUBMITAL IF |
| YOU WOULD LIKE. FBC 107.3.4.1 & FBC 107.3.4 |
| |
| 6) THE CALCULATIONS FOR ALLOWABLE OPENING AREA FOR THE |
| NORTH ELEVATION WILL NEED TO BE REVISED BASED ON THE |
| CHANGES TO THE WINDOW OPENINGS. THE APPROVED PLANS |
| INDICATE THE ALLOWABLE AREA OF OPENINGS IS 25 PERCENT. |
| PROVIDE THE CRITERIA THAT WAS USED TO DETERMINE THE 25 |
| PERCENT. IS THE BUILDING FULLY SPRINKLERED? WHAT IS THE |
| DISTANCE FROM THE WALL TO THE CENTER LINE OF THE |
| ADJACENT ALLEY? WHAT IS THE REQUIRED FIRE-RESISTANCE |
| RATING OF THE EXTERIOR BEARING WALLS, EXTERIOR |
| NON-BEARING WALLS AND EXTERIOR PRIMARY EXTERIOR FRAME? |
| FBC 705.8.1 |
| |
| 7) THE PLANS SHOW THAT A PORTION OF THE EXTERIOR GROUND |
| FLOOR COVERED AREA AT THE EAST ELEVATION IS BEING |
| ENCLOSED TO BECOME PART OF THE CONDITIONED BUILDING |
| SPACE. PLEASE INDICATE THE DIMENSIONS AND THE AREA OF |
| THIS ADDED SPACE ON THE PLANS. THIS IS REQUIRED TO BE |
| REVIEWED BY PALM BEACH COUNTY TO DETERMINE IF ANY |
| IMPACT FEES ARE DUE. PLANS REQUIRE REVIEW BY THE PBC |
| IMPACT FEE OFFICE. CALL (561) 233-5025. YOU WILL NEED |
| TO CHECK OUT ONE PLAN SET AND TAKE IT TO THAT OFFICE |
| FOR REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF |
| THE PAID RECEIPT AS APPLICABLE. PLEASE PROVIDE THE |
| MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO THE PBC |
| IMPACT FEE OFFICE. THE FORM CAN BE FOUND AT: |
| HTTP://DISCOVER.PBCGOV.ORG/PZB/AD |
| MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF |
| |
| 8) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |