2020-02-27 06:49:54PLUMBING 2ND REVIEW**DENIED**COMMENTS FROM 1ST REVIEW
 NOT ADDRESS:
 1) PROVIDE THE CLEAR FLOOR SPACE OF THE DRINKING
 FOUNTAINS. FBC-ACC 602.2
 2) PROVIDE CHANGE THE PICTURE DETAIL OF THE TOILET
 COMPARTMENT TOILET SHOWING THE HANDLE ON THE OPEN SIDE
 OF THE TOILET. FBC-ACC 604.6
 3) THE REAR GRAB BAR DETAIL ON SHT. A2.1.1 DETAIL #1
 AND 2 SHOW 12? FROM THE SIDE WALL. THIS SHOULD BE 12?
 FROM THE CENTERLINE OF THE TOILET AND @ 5? IF YOUR
 TOILET IS 17? FROM THE SIDE WALL. SEE FBC-ACC 604.5.2
 4) ON SHT. A2.1.1 DRINKING FOUNTAIN DETAIL #6 SHT.
 A2.1.1 PLEASE ADD NOTE OR SHOW THE MEASUREMENT IS TO
 THE SPOUT. FBC-ACC 602.4
 5) PROVIDE GRAB BAR HEIGHT DETAIL SHOWING MEASUREMENT
 IS TO THE TOP OF GRIPPING SURFACE. FBC-ACC 609.4
 6) PROVIDE MIRROR MOUNTING DETAIL SHOWING MAX 40? TO
 THE REFLECTIVE SURFACE OF THE MIRROR AND ALSO 1 OF THE
 MIRROR IN THE COMMON GROUP MUST COMPLY. FBC-ACC 603.3,
 213.3.4
 7) PROVIDE CLEAR FLOOR SPACE FOR AT LEAST 1 OF THE
 COMMON AREA BATHROOM SINKS. FBC-ACC 213.3.4
  