Date |
Text |
2020-01-07 15:02:27 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| NFPA 54 = NATIONAL FUEL GAS CODE |
| NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| NFPA 99 = HEALTH CARE FACILITIES CODE |
| NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| |
| 1ST REVIEW |
| PLUMBING COMMENTS: DENIED |
| A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| APPROVAL. |
| 1. PROVIDE CLEAR FLOOR SPACE FOR DRINKING FOUNTAIN |
| COMPLYING WITH FBC ACC 305.3 |
| 2. PER WPB FBC 107.2.1, PROVIDE SANITARY RISER DIAGRAM |
| FOR DRINKING FOUNTAIN. ARCHITECT TO PROVIDE FRAMING |
| AGAINST THE CONCRETE CHASE WALL TO ACCOMMODATE PIPING |
| AND FIXTURE SUPPORT. |
| 3. PROVIDE DETAIL (ISOMETRIC WILL SUFFICE) OF NEW |
| LAVATORIES CONNECTING FORMER URINAL/WATER CLOSET |
| WASTE/VENT PIPING. IF WATER CLOSET IS WALL HUNG, |
| PROVIDE DIRECTION FOR EFFECTIVELY CAPPING THE SANITARY |
| FITTING |
| 4. PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC |
| CHAPTERS 3 AND 6 PROVIDE DETAILS INDICATING THE |
| FOLLOWING: |
| A. WATER CLOSETS |
| *THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR |
| PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE |
| OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18 |
| INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC |
| ACC 604.2 |
| *CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES |
| MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND |
| 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR |
| WALL PER FBC ACC 604.3.1 |
| *THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG |
| MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE |
| REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR |
| WALL PER FBC ACC 604.5.1 |
| *THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG MINIMUM |
| AND EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12 |
| INCHES MINIMUM ON ONE SIDE AND 24 INCHES MINIMUM ON THE |
| OTHER SIDE PER FBC ACC 604.5.2*?FLUSH CONTROLS SHALL BE |
| HAND OPERATED OR AUTOMATIC. HAND OPERATED FLUSH |
| CONTROLS SHALL COMPLY WITH 309. FLUSH CONTROLS SHALL BE |
| LOCATED ON THE OPEN SIDE OF THE WATER CLOSET PER FBC |
| ACC 604.6 |
| *TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT |
| OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 |
| INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH |
| FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC |
| ACC 604.8. |
| B. DRINKING FOUNTAINS |
| *SPOUT OUTLETS SHALL BE 36 INCHES (915 MM) MAXIMUM |
| ABOVE THE FINISH FLOOR OR GROUND PER FBC ACC 602.4. |
| *THE SPOUT SHALL BE LOCATED 15 INCHES (380 MM) MINIMUM |
| FROM THE VERTICAL SUPPORT AND 5 INCHES (125 MM) MAXIMUM |
| FROM THE FRONT EDGE OF THE UNIT, INCLUDING BUMPERS PER |
| FBC ACC 602.5. |
| C. MIRRORS |
| *MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES |
| OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE |
| OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM |
| ABOVE THE FINISH FLOOR OR GROUND. |
| |
| |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-805-6715 |
| |
| 19120592 505 S FLAGLER FL 2 |