2020-01-14 12:28:552017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19120592
 ADD: 505 S. FLAGLER DR. / 2ND FLOOR & BRIDGE
 CONT: ANDERSON-MOORE CONSTRUCTION CORP.
 TEL: 561-348-4805
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JAN. 14TH/ 2020
 ACTION: DENIED
  
 1) THE LIFE SAFETY SHEET, ALS1.1:
  
 1A) UNDER THE HEADING CODE ANALYSIS IS MISSING THE
 TOTAL OCCUPANT LOAD FOR THIS FLOOR (1ST FLOOR). 2017
 FBC-B TABLE 1004.1.2. PLEASE UPDATE THE LIFE SAFETY
 SHEET.
  
 1B) THE DEMOLITION SHEET SHOWS IN THE RESTROOM ONE
 PLUMBING FIXTURE (WATER CLOSET/ URINAL) IS BEING
 ELIMINATED. THIS REVIEW THERE IS NO OCCUPANT LOAD
 PROVIDED FOR THE 1ST FLOOR. ONCE THE OCCUPANT LOAD IS
 KNOWN PLEASE REVIEW IN THE 2017 FBC-B TABLE 2902.1 THE
 REQUIRED MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES
 AND THEN PLEASE PROVIDE THE FIXTURE CALCULATION
 REQUIRED SEE SECTION 2902.1.1 OF THE 2017 FBC-B. TO
 DETERMINE THE OCCUPANT LOAD OF EACH SEX, THE TOTAL
 OCCUPANT LOAD SHALL BE DIVIDED IN HALF. TO DETERMINE
 THE REQUIRED NUMBER OF FIXTURES, THE FIXTURE RATIO OR
 RATIOS FOR EACH FIXTURE TYPE SHALL BE APPLIED TO THE
 OCCUPANT LOAD OF EACH SEX IN ACCORDANCE WITH TABLE
 2902.1.
  
 1C) BOTH SHEETS ALS1.1 & A.1.1.1 BOTH SHOW A NEW
 DRINKING FOUNTAIN NOTE # 9 ON SHEET A.1.1.1. THERE IS
 NO DETAIL OR SECTION SHOWING ELEVATIONS FOR THE
 DRINKING FOUNTAINS. IT CANNOT BE DETERMINED IF CODE
 COMPLIANCE WITH SECTION 211.2 OF THE 2017 ACCESSIBILITY
 CODE HAS BEEN MET.
  
 1D) SHEETS ALS1.1 & A.1.1.1 DOES NOT SHOW ELEVATIONS OF
 THE NEW DRINKING FOUNTAINS. THE 2ND CONCERN WITH THE
 DRINKING FOUNTAINS IS WITH THE HIGHER DRINKING FOUNTAIN
 COMPLYING WITH THE ACCESSIBILITY CODE SECTION 602.7.
 WITHOUT SEEING THE ELEVATION AND CONFIGURATION OF THE
 DRINKING FOUNTAIN, THE BOTTOM OF THE DRINKING FOUNTAIN
 CABINET IN RELATION TO FINISH FLOOR, PLEASE SHOW
 COMPLIANCE WITH LIMITATIONS OF PROTRUDING OBJECTS, SEE
 307.2 AND FIGURE 307.2 OF THE 2017 FBC-ACCESSIBILITY
 CODE.
  
 2) SHEET A1.1.4 AND S-1.0 BOTH SHOW THE USE OF ? INCH
 PLYWOOD STRUCTURAL 1, EXPOSURE 1, PLYWOOD SHEATHING ON
 THE BOTTOM SIDE OF THE SKY-BRIDGE, PAPER BACKED METAL
 LATH AND STUCCO. IN REVIEWING THE ALLOWABLE COMBUSTIBLE
 MATERIALS IN TYPE I AND TYPE II BUILDINGS 603.1 DOES
 NOT INDICATE THE USE OF SUCH MATERIALS IN A HORIZONTAL
 INSTALLATION ON THE EXTERIOR OF TYPE I CONSTRUCTION SEE
 603.1 OF THE FBC-B 2017.
 NEITHER DOES SECTION 718.5 COMBUSTIBLE MATERIALS IN
 CONCEALED SPACES IN TYPE I OR II CONSTRUCTION. ALSO
 REVIEW IN THE 2017 FBC-B PEDESTRIAN WALKWAYS. 3104.3
 CONSTRUCTION. THE PEDESTRIAN WALKWAY SHALL BE OF
 NONCOMBUSTIBLE CONSTRUCTION.
 EXCEPTIONS:
 1.COMBUSTIBLE CONSTRUCTION SHALL BE PERMITTED WHERE
 CONNECTED BUILDINGS ARE OF COMBUSTIBLE
 CONSTRUCTION.
 2.FIRE-RETARDANT-TREATED WOOD, IN ACCORDANCE WITH
 SECTION 603.1, ITEM 1.3, SHALL BE PERMITTED FOR
 THE ROOF CONSTRUCTION OF THE PEDESTRIAN WALKWAY WHERE
 CONNECTED BUILDINGS ARE A MINIMUM OF TYPE
 I OR II CONSTRUCTION.
  
 3) INSTEAD OF CONSIDERING THE RECONSTRUCTION OF THE
 SKY-BRIDGE AS PART OF A THRESHOLD BUILDING, WE ARE
 LOOKING THAT THE SKY-BRIDGE AS A SEPARATE BUILDING AS
 SECTION 3104.2 ALLOWS. THE SKY-BRIDGE ALSO IS LOCATED
 BENEATH THE 4TH FLOOR AND 50 FEET IN HEIGHT
 PREREQUISITES TO BE CONSIDERED FOR THRESHOLD BUILDINGS.
 THE CITY WOULD REQUIRE THE CONTRACTOR TO USE A 3RD
 PARTY ENGINEER FOR ALL BOLTED AND OR JOB-SITE WELDING.
  
 WELDED OR BOLTED CONNECTIONS
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE
 AMERICAN WELDING SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
 IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS
 FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU.
 PLEASE NOTE THIS REQUIREMENT MAYBE SUBJECT TO CHANGE.
 TODAY THERE IS NO B. O. OR ASSISTANT B.O. IN THE OFFICE
 TO PROVIDE GUIDANCE AND APPROVAL ON THIS MATTER.
  
 4) THE LIFE SAFETY SHEET LIST THE ALTERATION AS A LEVEL
 II, THIS IS TRUE FOR THE INTERIOR ALTERATION. WHEN
 VIEWING THE SKY-BRIDGE AS A SEPARATE BUILDING UNDER
 SECTION 3104.2 OF THE 2017 FBC-B THE ALTERATION TO THE
 SKY-BRIDGE WOULD BE CONSIDERED A LEVEL III. SEE THE
 2017 FBC-EXISTING BUILDING 907.4.2 SUBSTANTIAL
 STRUCTURAL ALTERATION.
  
 4A) 2017 FBC- EXISTING BUILDING CODE 907.4.1. WILL
 REQUIRE AN EVALUATION AND ANALYSIS OF THE SKY-BRIDGE
 FROM THE TIME THE SKY-BRIDGE WAS BUILT AND THE
 ADDITIONAL LOADING OF THE STRUCTURAL STEEL FRAME WORK
 WALLS/ ROOF FRAMING, GLAZING SYSTEM AND NEW ROOF
 SYSTEM.
 EXISTING BUILDING CODE 2017. 907.4.1 EVALUATION AND
 ANALYSIS. AN ENGINEERING EVALUATION AND ANALYSIS THAT
 ESTABLISHES THE STRUCTURAL ADEQUACY OF THE ALTERED
 STRUCTURE SHALL BE PREPARED BY A REGISTERED DESIGN
 PROFESSIONAL AND SUBMITTED TO THE CODE OFFICIAL.
  
 4B) THESE SAME REQUIREMENTS ARE FOUND UNDER LEVEL II
 ALTERATIONS AS WELL. EXISTING BUILDING CODE, BS] 907.2
 NEW STRUCTURAL ELEMENTS. NEW STRUCTURAL ELEMENTS SHALL
 COMPLY WITH SECTION 807.2.
  
 4C) THESE SAME REQUIREMENTS ARE FOUND UNDER LEVEL II
 ALTERATIONS AS WELL. [BS] 907.3 EXISTING STRUCTURAL
 ELEMENTS CARRYING GRAVITY LOADS. EXISTING STRUCTURAL
 ELEMENTS CARRYING GRAVITY LOADS SHALL COMPLY WITH
 SECTION 807.4.
  
 4D) THESE SAME REQUIREMENTS ARE FOUND UNDER LEVEL II
 ALTERATIONS AS WELL. [BS] 907.4 EXISTING STRUCTURAL
 ELEMENTS RESISTING LATERAL LOADS. ALL EXISTING ELEMENTS
 OF THE LATERAL FORCE-RESISTING SYSTEM SHALL COMPLY WITH
 THIS SECTION.
  
 5) THE DESIGN LOADS FOR THE ROOF SUPERIMPOSED DEAD
 LOADS LOOKS LIGHT FOR 2.2 CEILING AND ROOFING. AT THIS
 TIME THE ADDITIONAL LOADING CAN?T BE GIVEN. THE
 DESIGNER OF RECORD HAS NOT GIVEN ENOUGH INFORMATION FOR
 THE STEEL. THE SIZE OF THE TUBE STEEL IS GIVEN BUT NOT
 THE THICKNESS OF THE STEEL TUBES. 6X4X 0.025 INCH TUBE
 WEIGHTS 15.620 LBS. / LINEAR FT. WHEREAS THE 6X8X 0.025
 INCH TUBE WEIGHTS 22.420 LBS. / LINEAR FT. THE NEW
 LOADS TO BE SUPERIMPOSED ONTO THE SKY-BRIDGE WILL NEED
 TO BE ANALYZED TO SEE IF THE EXISTING STRUCTURE CAN
 HANDLE THE ADDITIONAL LOADS.
  
 6) SHEET S.2.0 WIND LOADS, IT APPEARS THERE TO BE A
 TYPO, THE VASD IS GIVEN AT 170 VULT AND THE VASD WIND
 SPEED TO BE 142 MPH. SHOULD BE 132MPH, VASD? 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 7) NOTICE ONLY/ NO ACTION NEEDS TO BE TAKEN. WIND
 PRESSURES GIVEN LOOK GOOD IF THE PRESSURES ARE TAKEN AT
 THE HEIGHT OF THE SKY-BRIDGE (SEPARATE BUILDING) AND
 NOT THE 15 STORY HIGHRISE.
  
 8) THIS REVIEW NO PRODUCT APPROVALS WERE SUBMITTED.
 PLEASE EITHER SUBMIT PRODUCT APPROVALS OR DECLARE IF
 THE DESIGNER OF RECORD WOULD PREFER TO HAVE THE PRODUCT
 APPROVALS BE DEFERRED SUBMITTALS.
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 9) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(B) WINDOWS & MULLIONS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 9A) IDENTIFY GLAZING/ MULLIONS. THE SUBMITTED PRODUCT
 APPROVALS THE ELEMENTS LISTED BELOW ARE NOT IDENTIFIED.
 PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 9B) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  