2020-01-14 12:28:55 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 19120592 |
| ADD: 505 S. FLAGLER DR. / 2ND FLOOR & BRIDGE |
| CONT: ANDERSON-MOORE CONSTRUCTION CORP. |
| TEL: 561-348-4805 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION. |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. JAN. 14TH/ 2020 |
| ACTION: DENIED |
| |
| 1) THE LIFE SAFETY SHEET, ALS1.1: |
| |
| 1A) UNDER THE HEADING CODE ANALYSIS IS MISSING THE |
| TOTAL OCCUPANT LOAD FOR THIS FLOOR (1ST FLOOR). 2017 |
| FBC-B TABLE 1004.1.2. PLEASE UPDATE THE LIFE SAFETY |
| SHEET. |
| |
| 1B) THE DEMOLITION SHEET SHOWS IN THE RESTROOM ONE |
| PLUMBING FIXTURE (WATER CLOSET/ URINAL) IS BEING |
| ELIMINATED. THIS REVIEW THERE IS NO OCCUPANT LOAD |
| PROVIDED FOR THE 1ST FLOOR. ONCE THE OCCUPANT LOAD IS |
| KNOWN PLEASE REVIEW IN THE 2017 FBC-B TABLE 2902.1 THE |
| REQUIRED MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES |
| AND THEN PLEASE PROVIDE THE FIXTURE CALCULATION |
| REQUIRED SEE SECTION 2902.1.1 OF THE 2017 FBC-B. TO |
| DETERMINE THE OCCUPANT LOAD OF EACH SEX, THE TOTAL |
| OCCUPANT LOAD SHALL BE DIVIDED IN HALF. TO DETERMINE |
| THE REQUIRED NUMBER OF FIXTURES, THE FIXTURE RATIO OR |
| RATIOS FOR EACH FIXTURE TYPE SHALL BE APPLIED TO THE |
| OCCUPANT LOAD OF EACH SEX IN ACCORDANCE WITH TABLE |
| 2902.1. |
| |
| 1C) BOTH SHEETS ALS1.1 & A.1.1.1 BOTH SHOW A NEW |
| DRINKING FOUNTAIN NOTE # 9 ON SHEET A.1.1.1. THERE IS |
| NO DETAIL OR SECTION SHOWING ELEVATIONS FOR THE |
| DRINKING FOUNTAINS. IT CANNOT BE DETERMINED IF CODE |
| COMPLIANCE WITH SECTION 211.2 OF THE 2017 ACCESSIBILITY |
| CODE HAS BEEN MET. |
| |
| 1D) SHEETS ALS1.1 & A.1.1.1 DOES NOT SHOW ELEVATIONS OF |
| THE NEW DRINKING FOUNTAINS. THE 2ND CONCERN WITH THE |
| DRINKING FOUNTAINS IS WITH THE HIGHER DRINKING FOUNTAIN |
| COMPLYING WITH THE ACCESSIBILITY CODE SECTION 602.7. |
| WITHOUT SEEING THE ELEVATION AND CONFIGURATION OF THE |
| DRINKING FOUNTAIN, THE BOTTOM OF THE DRINKING FOUNTAIN |
| CABINET IN RELATION TO FINISH FLOOR, PLEASE SHOW |
| COMPLIANCE WITH LIMITATIONS OF PROTRUDING OBJECTS, SEE |
| 307.2 AND FIGURE 307.2 OF THE 2017 FBC-ACCESSIBILITY |
| CODE. |
| |
| 2) SHEET A1.1.4 AND S-1.0 BOTH SHOW THE USE OF ? INCH |
| PLYWOOD STRUCTURAL 1, EXPOSURE 1, PLYWOOD SHEATHING ON |
| THE BOTTOM SIDE OF THE SKY-BRIDGE, PAPER BACKED METAL |
| LATH AND STUCCO. IN REVIEWING THE ALLOWABLE COMBUSTIBLE |
| MATERIALS IN TYPE I AND TYPE II BUILDINGS 603.1 DOES |
| NOT INDICATE THE USE OF SUCH MATERIALS IN A HORIZONTAL |
| INSTALLATION ON THE EXTERIOR OF TYPE I CONSTRUCTION SEE |
| 603.1 OF THE FBC-B 2017. |
| NEITHER DOES SECTION 718.5 COMBUSTIBLE MATERIALS IN |
| CONCEALED SPACES IN TYPE I OR II CONSTRUCTION. ALSO |
| REVIEW IN THE 2017 FBC-B PEDESTRIAN WALKWAYS. 3104.3 |
| CONSTRUCTION. THE PEDESTRIAN WALKWAY SHALL BE OF |
| NONCOMBUSTIBLE CONSTRUCTION. |
| EXCEPTIONS: |
| 1.COMBUSTIBLE CONSTRUCTION SHALL BE PERMITTED WHERE |
| CONNECTED BUILDINGS ARE OF COMBUSTIBLE |
| CONSTRUCTION. |
| 2.FIRE-RETARDANT-TREATED WOOD, IN ACCORDANCE WITH |
| SECTION 603.1, ITEM 1.3, SHALL BE PERMITTED FOR |
| THE ROOF CONSTRUCTION OF THE PEDESTRIAN WALKWAY WHERE |
| CONNECTED BUILDINGS ARE A MINIMUM OF TYPE |
| I OR II CONSTRUCTION. |
| |
| 3) INSTEAD OF CONSIDERING THE RECONSTRUCTION OF THE |
| SKY-BRIDGE AS PART OF A THRESHOLD BUILDING, WE ARE |
| LOOKING THAT THE SKY-BRIDGE AS A SEPARATE BUILDING AS |
| SECTION 3104.2 ALLOWS. THE SKY-BRIDGE ALSO IS LOCATED |
| BENEATH THE 4TH FLOOR AND 50 FEET IN HEIGHT |
| PREREQUISITES TO BE CONSIDERED FOR THRESHOLD BUILDINGS. |
| THE CITY WOULD REQUIRE THE CONTRACTOR TO USE A 3RD |
| PARTY ENGINEER FOR ALL BOLTED AND OR JOB-SITE WELDING. |
| |
| WELDED OR BOLTED CONNECTIONS |
| THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE |
| SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE |
| AMERICAN WELDING SOCIETY. |
| 2017 FBC-B 2204.1 WELDING |
| 2017 FBC-B 2204.2 BOLTING. |
| IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS |
| FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING |
| INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU. |
| PLEASE NOTE THIS REQUIREMENT MAYBE SUBJECT TO CHANGE. |
| TODAY THERE IS NO B. O. OR ASSISTANT B.O. IN THE OFFICE |
| TO PROVIDE GUIDANCE AND APPROVAL ON THIS MATTER. |
| |
| 4) THE LIFE SAFETY SHEET LIST THE ALTERATION AS A LEVEL |
| II, THIS IS TRUE FOR THE INTERIOR ALTERATION. WHEN |
| VIEWING THE SKY-BRIDGE AS A SEPARATE BUILDING UNDER |
| SECTION 3104.2 OF THE 2017 FBC-B THE ALTERATION TO THE |
| SKY-BRIDGE WOULD BE CONSIDERED A LEVEL III. SEE THE |
| 2017 FBC-EXISTING BUILDING 907.4.2 SUBSTANTIAL |
| STRUCTURAL ALTERATION. |
| |
| 4A) 2017 FBC- EXISTING BUILDING CODE 907.4.1. WILL |
| REQUIRE AN EVALUATION AND ANALYSIS OF THE SKY-BRIDGE |
| FROM THE TIME THE SKY-BRIDGE WAS BUILT AND THE |
| ADDITIONAL LOADING OF THE STRUCTURAL STEEL FRAME WORK |
| WALLS/ ROOF FRAMING, GLAZING SYSTEM AND NEW ROOF |
| SYSTEM. |
| EXISTING BUILDING CODE 2017. 907.4.1 EVALUATION AND |
| ANALYSIS. AN ENGINEERING EVALUATION AND ANALYSIS THAT |
| ESTABLISHES THE STRUCTURAL ADEQUACY OF THE ALTERED |
| STRUCTURE SHALL BE PREPARED BY A REGISTERED DESIGN |
| PROFESSIONAL AND SUBMITTED TO THE CODE OFFICIAL. |
| |
| 4B) THESE SAME REQUIREMENTS ARE FOUND UNDER LEVEL II |
| ALTERATIONS AS WELL. EXISTING BUILDING CODE, BS] 907.2 |
| NEW STRUCTURAL ELEMENTS. NEW STRUCTURAL ELEMENTS SHALL |
| COMPLY WITH SECTION 807.2. |
| |
| 4C) THESE SAME REQUIREMENTS ARE FOUND UNDER LEVEL II |
| ALTERATIONS AS WELL. [BS] 907.3 EXISTING STRUCTURAL |
| ELEMENTS CARRYING GRAVITY LOADS. EXISTING STRUCTURAL |
| ELEMENTS CARRYING GRAVITY LOADS SHALL COMPLY WITH |
| SECTION 807.4. |
| |
| 4D) THESE SAME REQUIREMENTS ARE FOUND UNDER LEVEL II |
| ALTERATIONS AS WELL. [BS] 907.4 EXISTING STRUCTURAL |
| ELEMENTS RESISTING LATERAL LOADS. ALL EXISTING ELEMENTS |
| OF THE LATERAL FORCE-RESISTING SYSTEM SHALL COMPLY WITH |
| THIS SECTION. |
| |
| 5) THE DESIGN LOADS FOR THE ROOF SUPERIMPOSED DEAD |
| LOADS LOOKS LIGHT FOR 2.2 CEILING AND ROOFING. AT THIS |
| TIME THE ADDITIONAL LOADING CAN?T BE GIVEN. THE |
| DESIGNER OF RECORD HAS NOT GIVEN ENOUGH INFORMATION FOR |
| THE STEEL. THE SIZE OF THE TUBE STEEL IS GIVEN BUT NOT |
| THE THICKNESS OF THE STEEL TUBES. 6X4X 0.025 INCH TUBE |
| WEIGHTS 15.620 LBS. / LINEAR FT. WHEREAS THE 6X8X 0.025 |
| INCH TUBE WEIGHTS 22.420 LBS. / LINEAR FT. THE NEW |
| LOADS TO BE SUPERIMPOSED ONTO THE SKY-BRIDGE WILL NEED |
| TO BE ANALYZED TO SEE IF THE EXISTING STRUCTURE CAN |
| HANDLE THE ADDITIONAL LOADS. |
| |
| 6) SHEET S.2.0 WIND LOADS, IT APPEARS THERE TO BE A |
| TYPO, THE VASD IS GIVEN AT 170 VULT AND THE VASD WIND |
| SPEED TO BE 142 MPH. SHOULD BE 132MPH, VASD? 107.2.1.2 |
| ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 7) NOTICE ONLY/ NO ACTION NEEDS TO BE TAKEN. WIND |
| PRESSURES GIVEN LOOK GOOD IF THE PRESSURES ARE TAKEN AT |
| THE HEIGHT OF THE SKY-BRIDGE (SEPARATE BUILDING) AND |
| NOT THE 15 STORY HIGHRISE. |
| |
| 8) THIS REVIEW NO PRODUCT APPROVALS WERE SUBMITTED. |
| PLEASE EITHER SUBMIT PRODUCT APPROVALS OR DECLARE IF |
| THE DESIGNER OF RECORD WOULD PREFER TO HAVE THE PRODUCT |
| APPROVALS BE DEFERRED SUBMITTALS. |
| 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| FOR REVIEW BY THE BUILDING OFFICIAL. |
| |
| DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. |
| |
| 9) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(B) WINDOWS & MULLIONS |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| |
| 9A) IDENTIFY GLAZING/ MULLIONS. THE SUBMITTED PRODUCT |
| APPROVALS THE ELEMENTS LISTED BELOW ARE NOT IDENTIFIED. |
| PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE |
| SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION |
| TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH |
| GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, |
| TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED |
| OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B |
| 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| |
| 9B) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY |
| ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES |
| FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL |
| LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF |
| ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR |
| BOTH INSULATION & THE BASE SHEET AS CALCULATED IN |
| COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117. |
| CALCULATION PREPARED, SIGNED AND |
| SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR |
| REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS & |
| CLADDING. |
| |
| 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| |
| |
| JAMES A. WITMER BN, PX, CBO |