2020-07-20 15:42:04 | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | | | MECHANICAL REVIEW APPROVED WITH PROVISOS: | | | | 1) IF THE WELDING OPTION IS SELECTED FOR THE RTU STAND | | CONNECTIONS THE FOLLOWING ARE REQUIRED TO BE APPROVED | | BY THE DESIGNER OF RECORD: | | AWS D1.1 CLAUSE 3.1: AT TIME OF INSPECTION PLEASE | | PROVIDE A WELD PROCEDURE SPECIFICATION; THE W.P.S. | | SPECIFIES THE REQUIRED ESSENTIAL VARIABLES INCLUDING: | | BASE MATERIALS, JOINTS, PROCESS, AND FILLER METALS TO | | BE USED. | | AWS D1.1 CLAUSE 4.15: AT TIME OF INSPECTION PLEASE | | PROVIDE A WELDER PERFORMANCE QUALIFICATION RECORD; THE | | W.P.Q.R. PROVIDES INFORMATION WHICH CAN BE USED TO | | VERIFY THE WELDER?S QUALIFICATION AND CERTIFICATION AS | | IT RELATES TO THE WELDING REQUIREMENTS OF THE PROJECT. | | 2) AS PER SECTION FBC M 508.1.1, THE TEMPERATURE | | DIFFERENTIAL BETWEEN THE MAKE?UP AIR AND THE | | CONDITIONED SPACE MUST NOT EXCEED 10 DEGREES F. |
|