 4TH MECHANICAL REVIEW DENIED:
  
 FBC M 602.1 - 602.2, PLEASE PROVIDE THE DOOR DETAILS
 FOR THE AIR HANDLER CLOSET AS THIS CLOSET APPEARS TO BE
 A PLENUM.
  
  
 PROVISOS:
  
 1) IF THE WELDING OPTION IS SELECTED FOR THE RTU STAND
 CONNECTIONS THE FOLLOWING ARE REQUIRED TO BE APPROVED
 BY THE DESIGNER OF RECORD:
 AWS D1.1 CLAUSE 3.1: AT TIME OF INSPECTION PLEASE
 PROVIDE A WELD PROCEDURE SPECIFICATION; THE W.P.S.
 SPECIFIES THE REQUIRED ESSENTIAL VARIABLES INCLUDING:
 BASE MATERIALS, JOINTS, PROCESS, AND FILLER METALS TO
 BE USED.
 AWS D1.1 CLAUSE 4.15: AT TIME OF INSPECTION PLEASE
 PROVIDE A WELDER PERFORMANCE QUALIFICATION RECORD; THE
 W.P.Q.R. PROVIDES INFORMATION WHICH CAN BE USED TO
 VERIFY THE WELDER?S QUALIFICATION AND CERTIFICATION AS
 IT RELATES TO THE WELDING REQUIREMENTS OF THE PROJECT.
  
 2) AS PER SECTION FBC M 508.1.1, THE TEMPERATURE
 DIFFERENTIAL BETWEEN THE MAKE-UP AIR AND THE
 CONDITIONED SPACE MUST NOT EXCEED 10 DEGREES F.
  
  
  
  