Plan Review Notes
Plan Review Notes For Permit 19120571
Permit Number 19120571
Review Stop P
Sequence Number 1
Notes
Date Text
2020-01-06 14:15:50CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 1. PER WPB FBC 107.2.1, PROVIDE SIZING PROCEDURE AND
 CALCULATIONS AS CALLED OUT IN STD. PDI-G101 USED IN
 DETERMINING THE GB-75 INTERCEPTOR.
 2. THE SPECIFIED FL1170 DOES NOT COMPLY WITH ASSE 1070
 AS REQUIRED BY FBC PL 416.5. PER WPB FBC 107.2.1,
 REVISE AND RESUBMIT.
 3. SPECIFY THAT A WATER TEMPERING DEVICE SHALL BE
 FURNISHED FOR THE LAVATORY IN ACCORDANCE WITH FBC PL
 416.5.
 4. PER WPB FBC 107.2.1, SPECIFY THE TANKLESS WATER
 HEATER AT THE LAVATORY AND PROVIDE MANUFACTURER?S
 SPECIFICATION FOR THE SAME.
 5. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER?S
 SPECIFICATION FOR THE GAS TANKLESS WATER HEATER.
 6. WATER RISER MISTAKENLY IDENTIFIES SECTIONS OF COLD
 WATER DISTRIBUTION AS HOT WATER WHICH IS FEEDING THE
 TANKLESS WATER HEATER AS WELL AS THE HAND SINK AND MOP
 SINK. EFFECTIVELY THERE IS NO HOT WATER TO THE HAND
 SINK OR MOP SINK. PER WPB FBC 107.2.1, CORRECT AND
 RESUBMIT. ADDITIONALLY, SHOW THE EXISTING COLD WATER
 SUPPLY TO THE EXISTING BATHROOM.
 7. PLAN PAGE 3.0P GAS INSTA-HOT WATER HEATER DETAIL HAS
 TWO NOTES: 1)WATER HEATER SET TO 140 DEGREES FOR
 WAREWASH ONLY; 1)WATER HEATER SET TO 110 DEGREES FOR
 HAND AND PREP SINKS ONLY. PER WPB FBC 107.2.1, PLEASE
 CLARIFY.
 8. PER WPB FBC 107.2.1, SPECIFY FAUCET FOR MOP SINK
 WHICH COMPLIES WITH FBC PL 608.2 BACKFLOW PROTECTION.
 9. PER WPB FBC 107.2.1, PROVIDE BACKFLOW PROTECTION IN
 COLD WATER SUPPLY TO THE ICEMAKER TO COMPLY WITH FBC PL
 608.3.
 10. PLAN SHEET 1.1A KITCHEN EQUIPMENT SCHEDULE; ITEM
 16, WAREWASHER (DISHWASHER) CALLS FOR A 2 INCH INDIRECT
 WASTE. PER WPB FBC 107.2.1, INDICATE ON THE SANITARY
 ISOMETRIC THAT INDIRECT WASTE AND WHERE IT DISCHARGES
 TO. COMPLY WITH FBC PL 802.1.7. ADDITIONALLY, INSURE
 THAT THE QUANTITY AND THE LOCATIONS OF FLOOR SINKS ARE
 THE SAME ON BOTH RISER AND FLOOR PLAN.
 11. A VENTED TRAP HAS BEEN PROVIDED AND IDENTIFIED AS A
 FLOOR SINK/ DR (DISHTABLE?). THE EQUIPMENT SCHEDULE
 CALL FOR A 1-1/2 INCH DIRECT CONNECTION TO THE
 SANITARY. PER WPB FBC 107.2.1, CLARIFY THAT THE VENTED
 TRAP IS PROVIDING THA AND IS NOT THE FLOOR SINK FOR THE
 DISHWASHER.
 12. PER WPB FBC 107.2.1, PROVIDE INDIVIDUAL INDIRECT
 WASTE FROM EACH WELL OF THE THREE-COMPARTMENT SINK
 DISCHARGING INDEPENDENTLY TO THE FLOOR SINK TO COMPLY
 FBC FL 802.1.
 13. PER WPB FBC 107.2.1, CLEARLY INDICATE HOW THE
 DISPOSAL OF COOLER AND FREEZER EVAPORATOR CONDENSATE
 WILL BE HANDLED.
 14. IF OCCUPANCY A-2 AND OCCUPANT LOAD CALCULATION IS
 NOT DISPUTED BY THE BUILDING PLANS EXAMINER, THEN THE
 FIXTURE REQUIREMENTS PER FBC PL SECTION 403 ARE
 COMPLIED WITH.
  
 END OF COMMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19120571 7310 GEORGIA AVE # 1
  