2020-01-06 14:15:50 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| NFPA 54 = NATIONAL FUEL GAS CODE |
| NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| NFPA 99 = HEALTH CARE FACILITIES CODE |
| NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| |
| 1ST REVIEW |
| PLUMBING COMMENTS: DENIED |
| 1. PER WPB FBC 107.2.1, PROVIDE SIZING PROCEDURE AND |
| CALCULATIONS AS CALLED OUT IN STD. PDI-G101 USED IN |
| DETERMINING THE GB-75 INTERCEPTOR. |
| 2. THE SPECIFIED FL1170 DOES NOT COMPLY WITH ASSE 1070 |
| AS REQUIRED BY FBC PL 416.5. PER WPB FBC 107.2.1, |
| REVISE AND RESUBMIT. |
| 3. SPECIFY THAT A WATER TEMPERING DEVICE SHALL BE |
| FURNISHED FOR THE LAVATORY IN ACCORDANCE WITH FBC PL |
| 416.5. |
| 4. PER WPB FBC 107.2.1, SPECIFY THE TANKLESS WATER |
| HEATER AT THE LAVATORY AND PROVIDE MANUFACTURER?S |
| SPECIFICATION FOR THE SAME. |
| 5. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER?S |
| SPECIFICATION FOR THE GAS TANKLESS WATER HEATER. |
| 6. WATER RISER MISTAKENLY IDENTIFIES SECTIONS OF COLD |
| WATER DISTRIBUTION AS HOT WATER WHICH IS FEEDING THE |
| TANKLESS WATER HEATER AS WELL AS THE HAND SINK AND MOP |
| SINK. EFFECTIVELY THERE IS NO HOT WATER TO THE HAND |
| SINK OR MOP SINK. PER WPB FBC 107.2.1, CORRECT AND |
| RESUBMIT. ADDITIONALLY, SHOW THE EXISTING COLD WATER |
| SUPPLY TO THE EXISTING BATHROOM. |
| 7. PLAN PAGE 3.0P GAS INSTA-HOT WATER HEATER DETAIL HAS |
| TWO NOTES: 1)WATER HEATER SET TO 140 DEGREES FOR |
| WAREWASH ONLY; 1)WATER HEATER SET TO 110 DEGREES FOR |
| HAND AND PREP SINKS ONLY. PER WPB FBC 107.2.1, PLEASE |
| CLARIFY. |
| 8. PER WPB FBC 107.2.1, SPECIFY FAUCET FOR MOP SINK |
| WHICH COMPLIES WITH FBC PL 608.2 BACKFLOW PROTECTION. |
| 9. PER WPB FBC 107.2.1, PROVIDE BACKFLOW PROTECTION IN |
| COLD WATER SUPPLY TO THE ICEMAKER TO COMPLY WITH FBC PL |
| 608.3. |
| 10. PLAN SHEET 1.1A KITCHEN EQUIPMENT SCHEDULE; ITEM |
| 16, WAREWASHER (DISHWASHER) CALLS FOR A 2 INCH INDIRECT |
| WASTE. PER WPB FBC 107.2.1, INDICATE ON THE SANITARY |
| ISOMETRIC THAT INDIRECT WASTE AND WHERE IT DISCHARGES |
| TO. COMPLY WITH FBC PL 802.1.7. ADDITIONALLY, INSURE |
| THAT THE QUANTITY AND THE LOCATIONS OF FLOOR SINKS ARE |
| THE SAME ON BOTH RISER AND FLOOR PLAN. |
| 11. A VENTED TRAP HAS BEEN PROVIDED AND IDENTIFIED AS A |
| FLOOR SINK/ DR (DISHTABLE?). THE EQUIPMENT SCHEDULE |
| CALL FOR A 1-1/2 INCH DIRECT CONNECTION TO THE |
| SANITARY. PER WPB FBC 107.2.1, CLARIFY THAT THE VENTED |
| TRAP IS PROVIDING THA AND IS NOT THE FLOOR SINK FOR THE |
| DISHWASHER. |
| 12. PER WPB FBC 107.2.1, PROVIDE INDIVIDUAL INDIRECT |
| WASTE FROM EACH WELL OF THE THREE-COMPARTMENT SINK |
| DISCHARGING INDEPENDENTLY TO THE FLOOR SINK TO COMPLY |
| FBC FL 802.1. |
| 13. PER WPB FBC 107.2.1, CLEARLY INDICATE HOW THE |
| DISPOSAL OF COOLER AND FREEZER EVAPORATOR CONDENSATE |
| WILL BE HANDLED. |
| 14. IF OCCUPANCY A-2 AND OCCUPANT LOAD CALCULATION IS |
| NOT DISPUTED BY THE BUILDING PLANS EXAMINER, THEN THE |
| FIXTURE REQUIREMENTS PER FBC PL SECTION 403 ARE |
| COMPLIED WITH. |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-805-6715 |
| |
| 19120571 7310 GEORGIA AVE # 1 |
| |