2019-12-31 17:08:311ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19120571
 12/31/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTION 301.1 FBC EX AND INDICATE WHAT
 COMPLIANCE METHOD WILL BE CHOSEN FOR THE PROPOSED
 OCCUPANCY. PLEASE NOTE THAT THE NEW COMMERCIAL KITCHEN
 APPEARS TO BE A CHANGE OF OCCUPANCY AS DEFINED IN
 SECTION 202, AND MAY REQUIRE SUBMITTAL OF ENERGY
 CALCULATIONS- SECTION C505.1 FBC EC.
  
 2) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW 5-TON SYSTEM IN ACCORDANCE WITH SECTION C403.2.1
 FBC EC.
  
 3) SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN
 EXHAUST HOODS, FIRE SUPPRESSION SYSTEMS, AND THE WALK
 IN COOLER- SECTION 107.2.1 WPB. PLEASE PLACE A BOLD
 NOTE ON THE PLAN FOR CLARIFICATION.
  
 4) SHEET 4.0M: PROVIDE MINIMUM VENTILATION CALCULATIONS
 FOR ALL ROOMS AND SPACES PER TABLE 403.3.1.1 FBC M.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 5) SHEET 4.0M: PROVIDE AN AIR BALANCE CALCULATION-
 SECTION 508.1.2 FBC M.
  
 6) SHEET 4.0M: A DUCT SMOKE DETECTOR IS REQUIRED IN THE
 SUPPLY AIR SYSTEM OF THE 5-TON AC SYSTEM PER SECTION
 606.2.1. PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED
 IF THE MANUFACTURER'S PERFORMANCE DATA INDICATES THE
 AIR HANDLER IS NOT CAPABLE OF PRODUCING OVER 2000 CFMS
 OF SUPPLY AIR.
  
 7) SHEET 4.0M: PROVIDE AN AUTOMATICALLY CONTROLLED
 SHUTOFF DAMPER- GRAVITY OR MOTORIZED- FOR THE O/A
 INTAKE DUCTS- SECTION C403.2.4.3 FBC EC.
  
 8) SHEET 4.0M: A NON-COMBUSTIBLE DOOR FOR THE AC CLOSET
 WILL BE REQUIRED IF THE RETURN IS NOT DUCTED DIRECTLY
 TO THE AIR HANDLER- SEE SECTION 602.2.1 FBC M.
  
 9) ADVISORY CONCERNING THE KITCHEN HOOD PERMIT: VERIFY
 THAT THE TEMPERATURE DIFFERENTIAL BETWEEN THE EXHAUST
 HOOD MAKEUP AIR AND THE AIR IN THE CONDITIONED SPACE
 DOES NOT EXCEED 10 DEGREES F- SECTION 508.1.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  