2019-12-31 17:08:31 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #19120571 |
| 12/31/19 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) REFER TO SECTION 301.1 FBC EX AND INDICATE WHAT |
| COMPLIANCE METHOD WILL BE CHOSEN FOR THE PROPOSED |
| OCCUPANCY. PLEASE NOTE THAT THE NEW COMMERCIAL KITCHEN |
| APPEARS TO BE A CHANGE OF OCCUPANCY AS DEFINED IN |
| SECTION 202, AND MAY REQUIRE SUBMITTAL OF ENERGY |
| CALCULATIONS- SECTION C505.1 FBC EC. |
| |
| 2) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE |
| NEW 5-TON SYSTEM IN ACCORDANCE WITH SECTION C403.2.1 |
| FBC EC. |
| |
| 3) SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN |
| EXHAUST HOODS, FIRE SUPPRESSION SYSTEMS, AND THE WALK |
| IN COOLER- SECTION 107.2.1 WPB. PLEASE PLACE A BOLD |
| NOTE ON THE PLAN FOR CLARIFICATION. |
| |
| 4) SHEET 4.0M: PROVIDE MINIMUM VENTILATION CALCULATIONS |
| FOR ALL ROOMS AND SPACES PER TABLE 403.3.1.1 FBC M. |
| PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND |
| PROVIDED CFMS OF OUTDOOR AIR. |
| |
| 5) SHEET 4.0M: PROVIDE AN AIR BALANCE CALCULATION- |
| SECTION 508.1.2 FBC M. |
| |
| 6) SHEET 4.0M: A DUCT SMOKE DETECTOR IS REQUIRED IN THE |
| SUPPLY AIR SYSTEM OF THE 5-TON AC SYSTEM PER SECTION |
| 606.2.1. PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED |
| IF THE MANUFACTURER'S PERFORMANCE DATA INDICATES THE |
| AIR HANDLER IS NOT CAPABLE OF PRODUCING OVER 2000 CFMS |
| OF SUPPLY AIR. |
| |
| 7) SHEET 4.0M: PROVIDE AN AUTOMATICALLY CONTROLLED |
| SHUTOFF DAMPER- GRAVITY OR MOTORIZED- FOR THE O/A |
| INTAKE DUCTS- SECTION C403.2.4.3 FBC EC. |
| |
| 8) SHEET 4.0M: A NON-COMBUSTIBLE DOOR FOR THE AC CLOSET |
| WILL BE REQUIRED IF THE RETURN IS NOT DUCTED DIRECTLY |
| TO THE AIR HANDLER- SEE SECTION 602.2.1 FBC M. |
| |
| 9) ADVISORY CONCERNING THE KITCHEN HOOD PERMIT: VERIFY |
| THAT THE TEMPERATURE DIFFERENTIAL BETWEEN THE EXHAUST |
| HOOD MAKEUP AIR AND THE AIR IN THE CONDITIONED SPACE |
| DOES NOT EXCEED 10 DEGREES F- SECTION 508.1.1 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |