Plan Review Notes
Plan Review Notes For Permit 19120571
Permit Number 19120571
Review Stop G
Sequence Number 1
Notes
Date Text
2020-01-06 15:18:09CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 GAS COMMENTS: DENIED
 1. PLAN SHEET 1.1A KITCHEN EQUIPMENT SCHEDULE; BLANK
 SPACE BETWEEN ITEM 1 AND ITEM 2 INDICATES ACTUAL
 SERVICES REQUIRED IDENTICAL TO ITEM 1. ITEM 1 INDICATES
 ONE (1) CONVECTION OVEN AT 90,000 BTUS. PLAN SHEET 3.0
 SHOWS TWO (2). PER WPB FBC 107.2.1 PLEASE CLARIFY.
 2. PER WPB FBC 107.2.1, SPECIFY THE TANKLESS WATER
 HEATER AT THE LAVATORY AND PROVIDE MANUFACTURER?S
 SPECIFICATION THE GAS TANKLESS WATER HEATER.
 3. PLAN PAGE 3.0P; GAS INSTA-HOT WATER HEATER DETAIL
 INDICATES ONE VENT. THE UNIT SPECIFIED IS SEALED
 COMBUSTION AND REQUIRES AN AIR INTAKE VENT AS WELL AS
 AN EXHAUST VENT. PER WPB FBC 107.2.1, PROVIDE CORRECT
 VENTING DETAILS, SUBMITTING A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE THE
 ROOF AND ANCHORING DETAILS OF THE GAS VENT(S) COMPLYING
 WITH FBC FG SECS. 502 THROUGH 505.
 4. PLAN PAGE 3.0P; PER WPB FBC 107.2.1, CORRECTLY
 IDENTIFY THE EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE.
 VALVE SHALL BE LOCATED BELOW THE CEILING. THE MANUAL
 SHUTOFF VALVE SHALL BE UPSTREAM. UNION TO BE DOWN
 STREAM OF MANUAL VALVE AHEAD OF EMERGENCY SHUT OFF
 VALVE. SECS. 10.4, 10.5 OF NFPA 96-08. SHOW LOCATION ON
 THE PLAN VIEW
 5. PER WPB FBC 107.2.1, INDICATE PIPE MATERIAL AS NOTED
 IN FBC FG TABLE 402.4(2).
 6. PER WPB FBC 107.2.1, SUBMIT CALCULATIONS FOR
 COMBUSTION AIR PER FBC FG 304.1.
 7. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND FBC FG
 402.2 AND 301.3. GAS APPLIANCES SHALL BE LISTED AND
 LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FBC FG 305.1.
  
 END OF COMMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19120571 7310 GEORGIA AVE # 1
  