2019-12-13 08:27:14 | PLAN REVIEW - NFIP - ELEVATION CERTIFICATE |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| BUILDING PLANS EXAMINER, PX3169 |
| 1&2 FAMILY PLANS EXAMINER, SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. REF. LINE A5 - LATITUDE AND LONGITUDE APPEAR TO BE |
| INCORRECT. IT IS RECOMMENDED THAT THE FRONT CENTER OF |
| THE STRUCTURE BE USED AS A REFENCE POINT. |
| |
| 2. REF. LINE A9 B) - STATE NUMBER OF FLOOD OPENINGS IN |
| ATTACHED GARAGE. |
| |
| 3. REF. LINE A9 C) - STATE NET AREA OF FLOOD OPENINGS. |
| |
| 4. REF. LINE A9 D) - PROPOSED FLOOD OPENINGS ARE |
| NON-ENGINEERED. PROVIDE DETAIL OF OPENINGS SIGNED AND |
| SEALED BY DESIGNER. |
| |
| 5. REF. LINE B8 - PROPERTY IS LOCATED IN FLOOD ZONES - |
| 2% FLOOD HAZARD; AE. |
| |
| 6. REF. LINE B9 - BASE FLOOD ELEVATIONS ARE 6 & 7. |
| |
| 7. REF. LINE C2 E) - DOCUMENT BOTTOM OF EQIPTMENT IS AT |
| OR ABOVE DFE AT FINISHED CONSTRUCTION ELEVATION |
| CERTIFICATE. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| |
| |
| |
| |
| |
| |