2020-01-07 13:51:50THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO DIMENSIONS INDICATED BETWEEN THE
 GENERATORS AND THE A/C INTAKES.
  
 THE LOCATION OF EXHAUST SHALL BE A MINIMUM OF 10' AND
 MUST NOT BE DOWNWIND WITHIN THE 10'(SEPARATION MUST BE
 EXTENDED IF DOWNWIND)
  
 PLEASE REIVIEW AND PROVIDE DETAILS.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  