Plan Review Notes For Permit 19120545 |
Permit Number |
19120545 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-01-07 13:51:50 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE ARE NO DIMENSIONS INDICATED BETWEEN THE | | GENERATORS AND THE A/C INTAKES. | | | | THE LOCATION OF EXHAUST SHALL BE A MINIMUM OF 10' AND | | MUST NOT BE DOWNWIND WITHIN THE 10'(SEPARATION MUST BE | | EXTENDED IF DOWNWIND) | | | | PLEASE REIVIEW AND PROVIDE DETAILS. | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|