Plan Review Notes
Plan Review Notes For Permit 19120531
Permit Number 19120531
Review Stop G
Sequence Number 1
Notes
Date Text
2019-12-16 05:44:121) WHO IS THE MANUFACTURER OF THIS UNIT? THERE IS NO
 MANUFACTURER'S NAME ON THE SPECS. SUBMIT THE COVER
 SHEET FOR THESE SPECS.WPB AMEND. TO FBC SEC. 107.2.1.
 2) THE UNIT SHALL BE LISTED AND LABELED. THE SUBMITTED
 DOCUMENTS DO NOT SHOW THIS.2017 FBC-FUEL GAS SEC.
 301.3.
 3) THE UNIT SHALL BE INSTALLED PER THE MANUFACTURER'S
 INSTALLATION MANUAL IN REGARDS TO OPERABLE WINDOWS,
 DOORS, AND BUILDING OPENINGS INCLUDING SOFFIT VENTS AND
 CRAWL SPACES. THE PAGE THAT HAS BEEN SUBMITTED SHOWING
 CLEARANCES DOES NOT HAVE THIS INFORMATION. SUBMIT THE
 CORRECT SHEET FROM THE INSTALLATION.2017 FBC-FUEL GAS
 SEC.305.1.
 4) SUBMIT TWO COPIES OF A HOUSE PLAN / FLOOR PLAN
 SHOWING THE LOCATION OF THE TANKLESS WATER HEATER AND
 THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR
 WINDOWS IN RELATION TO THE TANKLESS WATER HEATER. THE
 LOCATION OF THE TANKLESS WATER HEATER SHALL COMPLY WITH
 THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE HOUSE
 PLAN / FLOOR PLAN CAN BE HAND DRAWN. WPB AMEND. TO FBC
 SEC. 107.2.1.
 5) THE SUBMITTED SPECS NOTE THAT THIS UNIT OPERATES ON
 A MAXIMUM OF 10.5 INCHES OF WATER COLUMN OF GAS. IF THE
 INCOMING PRESSURE IS MORE THAN THIS, A REGULATOR WILL
 BE REQD. AT THE WATER HEATER. 2017 FBC-FUEL GAS
 SEC.305.1.
 6) SHOW THE LOCATION OF THE REGULATO (IF REQUIRED). A
 LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS
 SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4.
 7) . REGULATORS INSTALLED ON THE EXTERIOR OF THE
 BUILDING SHALL BE APPROVED FOR OUTDOOR INSTALLATION.
 IDENTIFY ON THE SPECIFICATION SHEETS WHICH MODEL
 REGULATOR IS BEING INSTALLED AND THE ORIFICE SIZE TO
 ENSURE THE REGULATOR CAN ACCOMMODATE THE BTU LOAD
 THROUGH THE REGULATOR.2017 FGC SEC.410.1, 2017 FBC-RES.
 SEC. G2421.1.
 8) WHERE CONNECTED TO RIGID PIPING, A UNION SHALL BE
 INSTALLED WITHIN ONE (1) FOOT OF EITHER SIDE OF THE
 REGULATOR. 2017 FBC-RESIDENTIAL SEC. G2421.2 (7), 2017
 FBC-FUEL GAS SEC. 410.2 (7).
 9) SHOW THE BTU LOAD OF THE EXISTING HEATER BEING
 REMOVED. IF THE BTU LOAD OF THE SYSTEM IS INCREASED DUE
 TO THE NEW TANKLESS, THE SYSTEM SHALL BE CHECKED TO
 INSURE THE ENTIRE SYSTEM IS SIZED PROPERLY.THE PLANS
 INDICATE AN EXISTING GAS METER. AND CITY RECORDS SHOW
 AN EXISTING GAS SYSTEM FOR THIS ADDRESS BUT DOES NOT
 SHOW A GAS WATER HEATER ON THE EXISTING GAS PLAN.. THE
 BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO
 THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.3, 401.4, 401.8, 402.1, 402.2, 402.3 OR
 FBCR SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
 10) SHOW THE TYPE OF PIPE AND PIPE SIZE ABOVEGROUND TO
 THE TANKLESS WATER HEATER AND REFERENCE THE SIZING
 TABLE FROM THE GAS CODE.FOR THIS PIPE. 2017 FBC-FUEL
 GAS SEC.401.8, 402.1.
 11) A PLUMBING PERMIT APPLICATION IS REQUIRED FOR THE
 CONNECTION OF THE WATER LINES.
  
 NOTE: I HAVE INCLUDED A COPY OF THE GAS RISER THAT THE
 CITY HAD ON FILE FOR THE CONTRACTOR TO USE IN SIZING
 THE SYSTEM WITH THE TANKLESS WATER HEATER.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  