2019-12-12 14:21:14 | PLAN REVIEW - BUILDING |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| BUILDING PLANS EXAMINER, PX3169 |
| 1&2 FAMILY PLANS EXAMINER, SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 2017 FBC 6TH CHPT. 1 |
| TEMPORARY MEMBRANE STRUCTURES |
| (TENTS) |
| CHPT. 1 FBC |
| |
| SECTION 108 |
| TEMPORARY STRUCTURES AND USES |
| |
| 108.1 GENERAL. THE BUILDING OFFICIAL IS AUTHORIZED TO |
| ISSUE A PERMIT FOR TEMPORARY STRUCTURES AND TEMPORARY |
| USES. SUCH PERMITS SHALL BE LIMITED AS TO TIME OF |
| SERVICE, BUT SHALL NOT BE PERMITTED FOR MORE THAN |
| 6MONTHS. THE BUILDING OFFICIAL IS AUTHORIZED TO GRANT |
| EXTENSIONS FOR |
| DEMONSTRATED CAUSE. |
| |
| 108.2 CONFORMANCE. TEMPORARY STRUCTURES AND USES SHALL |
| CONFORM TO THE STRUCTURAL STRENGTH, FIRE SAFETY, MEANS |
| OF EGRESS, ACCESSIBILITY, LIGHT, VENTILATION AND |
| SANITARY REQUIREMENTS OF THIS CODE AS NECESSARY TO |
| ENSURE PUBLIC HEALTH, SAFETY AND GENERAL WELFARE. |
| |
| 108.3 TEMPORARY POWER. THE BUILDING OFFICIAL IS |
| AUTHORIZED TO GIVE PERMISSION TO TEMPORARILY SUPPLY AND |
| USE POWER IN PART OF AN ELECTRIC INSTALLATION BEFORE |
| SUCH INSTALLATION HAS BEEN FULLY COMPLETED AND THE |
| FINAL CERTIFICATE OF COMPLETION HAS BEEN ISSUED. THE |
| PART COVERED BY THE TEMPORARY CERTIFICATE SHALL COMPLY |
| WITH THE REQUIREMENTS SPECIFIED FOR TEMPORARY LIGHTING, |
| HEAT OR |
| POWER IN CHAPTER 27 OF THE FLORIDA BUILDING CODE, |
| BUILDING. |
| |
| 108.4 TERMINATION OF APPROVAL. THE BUILDING OFFICIAL IS |
| AUTHORIZED TO TERMINATE SUCH PERMIT FOR A TEMPORARY |
| STRUCTURE OR USE AND TO ORDER THE TEMPORARY STRUCTURE |
| TO BE REMOVED OR USE TO BE DISCONTINUED. |
| |
| 2017 FBC 6TH CHPT. 31 |
| SPECIAL CONSTRUCTION |
| |
| SECTION 3103 |
| TEMPORARY STRUCTURES |
| |
| 3103.1 GENERAL. THE PROVISIONS OF SECTIONS 3103.1 |
| THROUGH 3103.4 SHALL APPLY TO STRUCTURES ERECTED FOR A |
| PERIOD OF LESS THAN 180 DAYS. TENTS AND OTHER MEMBRANE |
| STRUCTURES ERECTED FOR A PERIOD OF LESS THAN 180 DAYS |
| SHALL COMPLY WITH THE FLORIDA FIRE PREVENTION CODE. |
| THOSE ERECTED FOR A LONGER PERIOD SHALL COMPLY WITH |
| APPLICABLE SECTIONS OF THIS CODE. |
| 3103.1.1 CONFORMANCE. TEMPORARY STRUCTURES AND USES |
| SHALL CONFORM TO THE STRUCTURAL STRENGTH, FIRE SAFETY, |
| MEANS OF EGRESS, ACCESSIBILITY, LIGHT, VENTILATION AND |
| SANITARY REQUIREMENTS OF THIS CODE AS NECESSARY TO |
| ENSURE PUBLIC HEALTH, SAFETY AND GENERAL WELFARE. |
| 3103.1.2 PERMIT REQUIRED. TEMPORARY STRUCTURES THAT |
| COVER AN AREA GREATER THAN 120 SQUARE FEET (11.16 M2), |
| INCLUDING CONNECTING AREAS OR SPACES WITH A COMMON |
| MEANS OF EGRESS OR ENTRANCE THAT ARE USED OR INTENDED |
| TO BE USED FOR THE GATHERING TOGETHER OF 10 OR MORE |
| PERSONS, SHALL NOT BE ERECTED, OPERATED OR MAINTAINED |
| FOR ANY PURPOSE WITHOUT OBTAINING A PERMIT FROM THE |
| BUILDING OFFICIAL. |
| 3103.2 CONSTRUCTION DOCUMENTS. A PERMIT APPLICATION AND |
| CONSTRUCTION DOCUMENTS SHALL BE SUBMITTED FOR EACH |
| INSTALLATION OF A TEMPORARY STRUCTURE. THE CONSTRUCTION |
| DOCUMENTS SHALL INCLUDE A SITE PLAN INDICATING THE |
| LOCATION OF THE TEMPORARY STRUCTURE AND INFORMATION |
| DELINEATING THE MEANS OF EGRESS AND THE OCCUPANT LOAD. |
| 3103.3 LOCATION. TEMPORARY STRUCTURES SHALL BE LOCATED |
| IN ACCORDANCE WITH THE REQUIREMENTS OF TABLE 602 BASED |
| ON THE FIRE-RESISTANCE RATING OF THE EXTERIOR WALLS FOR |
| THE PROPOSED TYPE OF CONSTRUCTION. |
| 3103.4 MEANS OF EGRESS. TEMPORARY STRUCTURES SHALL |
| CONFORM TO THE MEANS OF EGRESS REQUIREMENTS OF CHAPTER |
| 10 AND SHALL HAVE AN EXIT ACCESS TRAVEL DISTANCE OF 100 |
| FEET (30 480 MM) OR LESS. |
| |
| APPLICANTION CHECKLIST |
| ALL STRUCTURES INSTALLED FOR LESS THAN 180 DAYS, |
| GREATER THAN 120 SQ. FT. WITH 10 OR MORE OCCUPANTS |
| * APPLICATION NEEDS TO BE SUBMITTED AT LEAST TWO WEEKS |
| PRIOR TO EVENT |
| 1. PERMIT APPLICATION |
| A. PROVIDE EVENT FUNCTION |
| B. ADDRESS OF EVENT |
| C. WORK DESCRIPTION ? I.E. NUMBER AND SIZE OF TENTS |
| D. OWNER AND CONTRACTOR INFO. |
| E. VALUE ? ATTACH COPY OF CONTRACT WITH OWNER |
| F. SPECIFY DATES OF INSTALLATION AND REMOVAL |
| 2. SITE PLAN |
| A. SHOW TO SCALE THE SIZE AND LOCATION OF NEW |
| CONSTRUCTION AND EXISTING |
| STRUCTURES ON THE SITE? |
| B. SHOW DISTANCE TO LOT LINES AND OTHER STRUCTURES PER |
| FBC CHPT. 6, SEC. 602 |
| C. PROVIDE SQUARE FOOTAGE |
| D. PROVIDE ESTIMATED OCCUPANCY CONTENT OF EACH TENT |
| E. PROVIDE ACCESSIBLE ROUTE FROM PARKING TO TENT |
| ENTRANCE |
| F. IDENTIFY MEANS OF EGRESS PER CHPT. 10 |
| G. PROVIDE ACCESSIBLE ROUTE FROM TENT TO ACCESSIBLE |
| RESTROOMS |
| H. ACCESSIBLE RESTROOMS SHALL BE LOCATED WITHIN 500 |
| FEET OF TENT |
| 2. FOUNDATION/TIE DOWN |
| A. PROVIDE DETAIL OF TIE DOWN FOR UPLIFT |
| B. PROVIDE DETAIL OF ANCHORS FOR TENT LEG LATERAL |
| MOVEMENT |
| 3. CONFORMANCE PER SECTION 3103.1.1 |
| TEMPORARY STRUCTURES AND USES SHALL CONFORM TO THE |
| STRUCTURAL STRENGTH, FIRE SAFETY, MEANS OF EGRESS, |
| ACCESSIBILITY, LIGHT, VENTILATION AND SANITARY |
| REQUIREMENTS OF THIS CODE AS NECESSARY TO ENSURE PUBLIC |
| HEALTH, SAFETY AND GENERAL WELFARE. |
| A. STRUCTURAL STRENGTH PER FBC CHPT. 16 ? FOR |
| STRUCTURES WITH SPANS OF 30 FEET OR GREATER. |
| B. FIRE SAFETY ? PROVIDE FLAME SPREAD TEST REPORTS PER |
| NFPA 701 FOR EACH TENT |
| C. MEANS OF EGRESS 1) OPEN SIDES ? NO LIFE SAFETY PLAN |
| REQUIRED. |
| 2) CLOSED SIDES ? PROVIDE LIFE SAFETY PLAN |
| A) STATE OCCUPANT LOAD. |
| B) IDENTIFY MEANS OF EGRESS. |
| C) IDENTIFY PATH OF TRAVEL ? 100 FT. OR LESS TO |
| EXIT. |
| D) PROVIDE FLOOR LAYOUT OF EVENT. |
| D. ACCESSIBILITY 1) IDENTIFY ACCESSIBLE ROUTE ON SITE |
| PLAN |
| E. LIGHT 1) OPEN SIDES ? N/A |
| 2) CLOSED SIDES ? PER SEC. 1008.2.1 > 1 FOOT CANDLE |
| F. VENTILATION 1) OPEN SIDES ? N/A |
| 2) CLOSED SIDES ? PER SEC. 1203 |
| G. SANITARY 1) IDENTIFY EXISTING PERMANENT FACILITIES |
| ON SITE PLAN |
| 2) PROVIDE PORTABLE FACILITIES PER TABLE 2902. |
| _______________________________________________________ |
| _________________ |
| |
| |
| *ADDITIONAL REQUIREMENTS |
| FOR TEMPORARY MEMBRANE STRUCTURES (TENTS) WITH A SPAN |
| OF 30 FEET OR GREATER IN ANY DIRECTION: |
| |
| A. PROVIDE DETAILS OF STRUCTURAL CONNECTIONS. INCLUDE |
| BASEPLATE/TIEDOWN DETAILS. |
| B. PROVIDE STRUCTURAL EVALUATION OF STRUCTURE. |
| |
| THESE DOCUMENTS SHALL BE REVIEWED, SIGNED AND SEALED BY |
| A DESIGN PROFESSIONAL. |
| |
| OPTION TO ABOVE REQUIREMENT ? |
| YOU MAY PLACE A STATEMENT ON YOUR PLAN THAT THE TENT |
| WILL BE REMOVED IF WINDS ARE EXPECTED TO EXCEED 30 MPH |
| |
| _______________________________________________________ |
| _________________ |
| |
| |
| **ADDITIONAL REQUIREMENTS |
| FOR TEMPORARY MEMBRANE STRUCTURES (TENTS) WITH A SPAN |
| OF 40 FEET OR GREATER IN ANY DIRECTION: |
| |
| A. PROVIDE DETAILS OF STRUCTURAL CONNECTIONS. INCLUDE |
| BASEPLATE/TIEDOWN DETAILS. |
| B. PROVIDE STRUCTURAL EVALUATION OF STRUCTURE. |
| |
| THESE DOCUMENTS SHALL BE REVIEWED, SIGNED AND SEALED BY |
| A DESIGN PROFESSIONAL. |
| |
| NO EXCEPTIONS |
| |
| _______________________________________________________ |
| _________ |
| |
| ***ADDITIONAL REQUIREMENTS |
| FOR TEMPORARY MEMBRANE STRUCTURES (TENTS) WITH AN |
| ?ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE |
| FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN |
| AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| PERSONS?. |
| |
| FLORIDA STATUTE 553.79 ?THREHOLD STRUCTURE? SHALL APPLY |
| |
| A. PROVIDE THRESHOLD INSPECTOR AGREEMENT ? WILL BE |
| PROVIDED TO APPLICANT |
| B. PROVIDE THRESHOLD INSPECTION PLAN |
| C. PROVIDE AFFIDAVIT ?CERTIFICATE OF CODE COMPLIANCE? |
| _______________________________________________________ |
| _______________ |
| |
| |