Plan Review Notes For Permit 19120500 |
Permit Number |
19120500 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2020-06-22 14:19:02 | NEW BUILDING SHELL | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) PRODUCT APPROVAL (18-0129.06 AND 17-1218.09) LISTED | | ON DRAWING A-6.0 FOR THE STOREFRONT GLAZING AND SGD | | DOES NOT MEET THE LARGE MISSILE IMPACT REQUIREMENTS PER | | FBC 1609.1.2 (1) - PLEASE PROVIDE PRODUCT APPROVAL FOR | | THE REQUIRED SHUTTERS. | | | | | | ITEMS TO PROVISO = | | 1) WILL NEED TO PROVIDE SIGNED AND SEALED LOUVER SYSTEM | | DETAILS TO COMPLY WITH THE DESIGN WIND LOADS. FBC 1609 | | 2) WILL NEED TO PROVIDE SIGNED AND SEALED METAL CANOPY | | DETAILS TO COMPLY WITH THE DESIGN WIND LOADS. FBC 1609 | | 3) WILL NEED TO PROVIDE A SIGNED AND SEALED SOIL REPORT | | (GEOTECHNICAL REPORT) TO VERIFY THE REQUIRED SOIL | | BEARING CAPACITY PER NOTES ON THE DRAWINGS. | | |
|