2020-04-30 12:42:02ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) NEED TO ADD AN OUTLET AT THE SERVICE LOCATION PER
 210.64
  
 210.64 ELECTRICAL SERVICE AREAS AT LEAST ONE 125-VOLT,
 SINGLE-PHASE, 15- OR 20-AMPERE-RATED RECEPTACLE OUTLET
 SHALL BE INSTALLED WITH IN 15 M (50 FT) OF THE
 ELECTRICAL SERVICE EQUIPMENT.
  
 2) NEED AIC CALCULATION AND LABLES FOR SERVICE
 EQUIPMENT. 110.24
  
 110.24 AVAILABLE FAULT CURRENT ( A) FIELD MARKING.
 SERVICE EQUIPMENT IN OTHER THAN DWELLING UNITS SHALL BE
 LEGIBLY MARKED IN THE FIELD WITH THE MAXIMUM AVAILABLE
 FAULT CURRENT. THE FIELD MARKING(S) SHALL INCLUDE THE
 DATE THE FAULT-CURRENT CALCULATION WAS PERFORMED AND BE
 OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT
 INVOLVED
  
 3) INTERSYSTEM BONDING CONNECTION TO BE INSTALLED AT
 SERVICE. 250.94
  
 250.94 BONDING FOR OTHER SYSTEMS AN INTERSYSTEM BONDING
 TERMINATION FOR CONNECTING INTERSYSTEM BONDING
 CONDUCTORS REQUIRED FOR OTHER SYSTEMS SHALL BE PROVIDED
 EXTERNAL TO ENCLOSURES AT THE SERVICE EQUIPMENT OR
 METERING EQUIPMENT ENCLOSURE AND AT THE DISCONNECTING
 MEANS FOR ANY ADDITIONAL BUILDINGS OR STRUCTURES.