Plan Review Notes For Permit 19120500 |
Permit Number |
19120500 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2020-04-28 13:49:10 | NEW BUILDING | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) PRODUCT APPROVAL (14-1204.10) LISTED ON DRAWING | | A-6.0 FOR THE STOREFRONT GLAZING DOES NOT MEET IMPACT | | REQUIREMENTS FBC 1609.1.2 - PLEASE PROVIDE PRODUCT | | APPROVAL NUMBER FOR THE REQUIRED SHUTTERS. | | 2) PLEASE PROVIDE PRODUCT APPROVAL FOR THE METAL | | ROOFING. | | 3) PLEASE PROVIDE A SIGNED AND SEALED SOIL REPORT | | (GEOTECHNICAL REPORT) TO VERIFY THE REQUIRED SOIL | | BEARING CAPACITY PER DRAWINGS. | | 4) PLEASE PROVIDE SIGNED AND SEALED SIDING ATTACHMENT | | DETAILS OR PRODUCT APPROVAL TO COMPLY WITH WIND DESIGN | | PRESSURES SHOWN ON THE DRAWINGS. | | 5) PLEASE PROVIDE SIGNED AND SEALED LOUVER SYSTEM | | DETAILS TO COMPLY WITH THE DESIGN WIND LOADS. | | 6) PLEASE PROVIDE SIGNED AND SEALED METAL CANOPY | | DETAILS TO COMPLY WITH THE DESIGN WIND LOADS. | | 7) COVER SHEET SHOWS CODE USED "RESIDENTIAL" SHOULD BE | | "BUILDING". | | |
|