Plan Review Notes
Plan Review Notes For Permit 19120500
Permit Number 19120500
Review Stop E
Sequence Number 1
Notes
Date Text
2020-02-16 07:58:46CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PAGE E.1.1 IN THE SCOPE OF WORK FOR LOTS NOTE #3 HAS
 2017 NEC
  
 2) PAGE E.2.1 IN NOTE #2 YOU QUOTE NFPA-72-2010 SHOULD
 BE 2013, AND NFPA-101-2012 SHOULD BE 2015
  
 3) NOT SURE HOW TO REVIEW THESE PLANS IF FOR
 RESIDENTIAL THERE ARE MANY ITEMS MISSING. I WILL CHECK
 WITH MY SUPERVISOR FOR RECOMMENDATIONS.