Plan Review Notes
Plan Review Notes For Permit 19120500
Permit Number 19120500
Review Stop B
Sequence Number 1
Notes
Date Text
2020-02-07 11:27:54BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19120500
 REVIEWED: FEBRUARY 6, 2020
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 DUE TO THE FACT THAT THESE STRUCTURES MAY BE
 RESIDENTIAL AND COMMERCIAL IN NATURE SOME CROSSOVER IN
 BUILDING CODE REVIEW WILL OCCUR. THE MOST STRINGENT OF
 THE CODES WILL APPLY.
 - PLEASE USE CODE REFERENCE IN BRACKETS AT EACH COMMENT
 AND REFER TO CODE INDEX AT THE TOP OF PAGE FOR THE CODE
 BOOK WHERE THAT THE COMMENT REFERENCES.
 419.1 FBC[B]GENERAL. A LIVE/WORK UNIT SHALL COMPLY WITH
 SECTIONS 419.1 THROUGH 419.9.
 - WHILE NOT CLARIFIED FOR THIS PERMIT IF LIVE WORK IS
 SPECIFIED FOR BUILD OUT PLEASE APPLY CHAPTER 4 SPECIAL
 REQUIREMENTS.
  
 1) 107.2.5 FBC[AMENDED] DEMOLITION PLAN.
 - PLEASE PUT FOR REFERENCE ONLY ON DEMO SHEET A1.0D.
 REMOVAL OF STRUCTURES REQUIRES A SEPARATE DEMOLITION
 PERMIT THAT HANDLES ALL ASSPECTS OF UTILITY
 DISCONNECTS.
  
 2) 401.2 FBC[RE] PROVIDE ENERGY CALCULATIONS TO MEET
 REQUIREMENTS IN R401.2 RESIDENTIAL ENERGY CODE. CHOOSE
 METHOD IN R401.2 AND SUPPLY DOCUMENTATION.
 - PLEASE SUPPLY ENERGY CALCULATIONS WITH CHECKLISTS AND
 EPL CARD. EVEN THOUGH THE PLANS ARE FOR SHELL ONLY, THE
 THERMAL ENVELOPE NEEDS TO BE COMPLETED BY CHOSEN METHOD
 AND DOCUMENTS PROVIDED TO SHOW COMPLIANCE.
  
 3) 107.5.3 FBC[AMENDED]ADD SQUARE FOOTAGE OF SPACE
 UNDER AIR, OUTDOOR DECK SPACE AND TOTAL SPACE FOR THIS
 BUIL;DING.
 - SINCE THIS IS SHARED DECK SPLIT THE SQ. FOOTAGE
 BETWEEN THE BUILDINGS.
  
 4) 107.3.5.3 FBC[AMENDED] PROVIDE SEDIMENT CONTROL TO
 KEEP CONSTRUCTION DEBRIS FROM ENTERING ADJACENT
 PROPERTIES AND STORM DRAINS DURING CONSTRUCTION. YOU
 CAN JUST ADD SILT FENCE DETAIL AND HOW DRAINS ARE
 PROTECTED TO THE DRAINAGE PLAN. SOME ENGINEERING
 STANDARD DETAILS CAN BE USED FROM WPB WEBSITE-POLLUTION
 CONTROL. HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUB
 LIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 5) [FBC 107.5][FBC 110.9][FBC R401.3]SHEET C503 FOR
 DRAINAGE SHOWS THE STUCTURES TO BE PLACED ON PADS.
 PLEASE ADJUST DRIANAGE PLAN TO ACCOUNT FOR STRUCTURES
 TO BE BUILT ON RAISED PIERS. SHOW HOW WATER WILL BE
 KEPT AWAY FROM THE CRAWL SPACE AND HOW DRAINAGE WORK
 BETWEEN STRUCTURES AS WATER DRAINS THROUGH THE DECK.
  
 6) 408.1 FBC[R] VENTILATION. THE UNDER-FLOOR SPACE
 BETWEEN THE BOTTOM OF THE FLOOR JOISTS AND THE EARTH
 UNDER ANY BUILDING (EXCEPT SPACE OCCUPIED BY A
 BASEMENT) SHALL HAVE VENTILATION OPENINGS THROUGH
 FOUNDATION WALLS OR EXTERIOR WALLS.
 - THERE IS PLENTY OF VENTILATION, BUT TYPICALLY THE
 OPENINGS FOLLOW R408.1 WHERE IT STATES THAT OPENINGS
 ARE TO BE COVERED WITH MATERIAL PROVIDED THAT THE LEAST
 DIMENSION SHALL NOT EXCEED 1/4 INCH.
  
 7) 408.4 FBC[R] ACCESS TO UNDER FLOOR SPACE. ACCESS
 OPENINGS THROUGH THE FLOOR SHALL BE A MINIMUM OF 18
 INCHES BY 24 INCHES. OPENINGS THROUGH A PERIMETER WALL
 SHALL BE NOT LESS THAN 16 INCHES BY 24 INCHES.
 - PLEASE INDICATE WHERE ACCESS WILL BE PROVIDED.
  
 8) PROVIDE DOCUMENTATION OF UNDER FLOOR INSULATION.
 DOES IT PROVIDE VAPOR BARRIER?
  
 9) F101.6 FBC[B]APPENDIX F. PIER AND WOOD CONSTRUCTION.
 F101.6.1 SILL LESS THAN 12 INCHES ABOVE GROUND.
 BUILDINGS NOT PROVIDED WITH A CONTINUOUS FOUNDATION
 SHALL BE PROVIDED WITH PROTECTION AGAINST RODENTS AT
 GRADE BY PROVIDING EITHER AN APRON IN ACCORDANCE WITH
 SECTION F101.6.1.1 OR A FLOOR SLAB IN ACCORDANCE WITH
 SECTION F101.6.1.2. F101.6.1.1 APRON. WHERE AN APRON IS
 PROVIDED, THE APRON SHALL BE NOT LESS THAN 8 INCHES
 (203 MM) ABOVE, NOR LESS THAN 24 INCHES (610 MM) BELOW,
 GRADE. THE APRON SHALL NOT TERMINATE BELOW THE LOWER
 EDGE OF THE SIDING MATERIAL. THE APRON SHALL BE
 CONSTRUCTED OF AN APPROVED NONDECAYABLE,
 WATER-RESISTANT RODENTPROOFING MATERIAL OF REQUIRED
 STRENGTH AND SHALL BE INSTALLED AROUND THE ENTIRE
 PERIMETER OF THE BUILDING. WHERE CONSTRUCTED OF MASONRY
 OR CONCRETE MATERIALS, THE APRON SHALL BE NOT LESS THAN
 4 INCHES (102 MM) IN THICKNESS.
 - THE PROPOSED LATTICE AT THE UNDER FLOOR AREAS WOULD
 CREATE ACCESS FOR CRITTERS TO THE UNDERSIDE OF
 STRUCTURE AND EXPOSED INSULATION. PLEASE REVIEW
 REQUIRMENTS FOR VENTILATION AND APPENDIX F FOR RODENT
 PROOFING.
  
 10) 105.10 FBC[B]CERTIFICATE OF PROTECTIVE TREATMENT
 FOR PREVENTION OF TERMITES. A WEATHER-RESISTANT
 JOB-SITE POSTING BOARD SHALL BE PROVIDED TO RECEIVE
 DUPLICATE TREATMENT CERTIFICATES AS EACH REQUIRED
 PROTECTIVE TREATMENT IS COMPLETED, PROVIDING A COPY FOR
 THE PERSON THE PERMIT IS ISSUED TO AND ANOTHER COPY FOR
 THE BUILDING PERMIT FILES. THE TREATMENT CERTIFICATE
 SHALL PROVIDE THE PRODUCT USED, IDENTITY OF THE
 APPLICATOR, TIME AND DATE OF THE TREATMENT, SITE
 LOCATION, AREA TREATED, CHEMICAL USED, PERCENT
 CONCENTRATION AND NUMBER OF GALLONS USED, TO ESTABLISH
 A VERIFIABLE RECORD OF PROTECTIVE TREATMENT. IF THE
 SOIL CHEMICAL BARRIER METHOD FOR TERMITE PREVENTION IS
 USED, FINAL EXTERIOR TREATMENT SHALL BE COMPLETED PRIOR
 TO FINAL BUILDING APPROVAL.
 - NO NOTES FOUND ON PLAN ABOUT TERMITE TREATMENT.
 PLEASE ADD OR LET ME KNOW WHAT SHEET THEY ARE LOCATED
 ON.
  
 105.11 FBC[B]NOTICE OF TERMITE PROTECTION. A PERMANENT
 SIGN WHICH IDENTIFIES THE TERMITE TREATMENT PROVIDER
 AND NEED FOR REINSPECTION AND TREATMENT CONTRACT
 RENEWAL SHALL BE PROVIDED. THE SIGN SHALL BE POSTED
 NEAR THE WATER HEATER OR ELECTRIC PANEL.
 - NO NOTES FOUND ON PLAN ABOUT TERMITE TREATMENT.
 PLEASE ADD OR LET ME KNOW WHAT SHEET THEY ARE LOCATED
 ON.
  
 1816.1 FBC[B]TERMITE PROTECTION. TERMITE PROTECTION
 SHALL BE PROVIDED BY REGISTERED TERMITICIDES, INCLUDING
 SOIL APPLIED PESTICIDES, BAITING SYSTEMS, AND
 PESTICIDES APPLIED TO WOOD, OR OTHER APPROVED METHODS
 OF TERMITE PROTECTION LABELED FOR USE AS A PREVENTATIVE
 TREATMENT TO NEW CONSTRUCTION. SEE SECTION 202,
 ?REGISTERED TERMITICIDE.? UPON COMPLETION OF THE
 APPLICATION OF THE TERMITE PROTECTIVE TREATMENT, A
 CERTIFICATE OF COMPLIANCE SHALL BE ISSUED TO THE
 BUILDING DEPARTMENT BY THE LICENSED PEST CONTROL
 COMPANY THAT CONTAINS THE FOLLOWING STATEMENT: ?THE
 BUILDING HAS RECEIVED A COMPLETE TREATMENT FOR THE
 PREVENTION OF SUBTERRANEAN TERMITES. TREATMENT IS IN
 ACCORDANCE WITH RULES AND LAWS ESTABLISHED BY THE
 FLORIDA DEPARTMENT OF AGRICULTURE AND CONSUMER
 SERVICES.?
  
 11) 806.5 FBC[R] UNVENTED ATTIC AND UNVENTED ENCLOSED
 RAFTER ASSEMBLIES. 5.1.2. WHERE AIR-PERMEABLE
 INSULATION IS PROVIDED INSIDE THE BUILDING THERMAL
 ENVELOPE, IT SHALL BE INSTALLED IN ACCORDANCE WITH
 SECTION 5.1.1. IN ADDITION TO THE AIR-PERMEABLE
 INSULATION INSTALLED DIRECTLY BELOW THE STRUCTURAL
 SHEATHING, RIGID BOARD OR SHEET INSULATION SHALL BE
 INSTALLED DIRECTLY ABOVE THE STRUCTURAL ROOF SHEATHING
 IN ACCORDANCE WITH THE R-VALUES IN TABLE R806.5 FOR
 CONDENSATION CONTROL.
 - PLEASE REVIEW THIS SECTION FOR AIR PERMEABLE
 INSULATION AT ROOF DECK FOR CONDENSATION CONTROL. ALSO,
 PROVIDE R-VALUE OF ALL INSULATION IN ENERGY CALCULATION
 DOCUMENTS.
  
 12) 905.1.1 FBC[R] ASPHALT SHINGLES SHALL BE USED ONLY
 ON ROOF SLOPES OF TWO UNITS VERTICAL IN 12 UNITS
 HORIZONTAL (2:12) OR GREATER
  
 905.2.2 FBC[R] & 905.1.1 FBC[R] FOR ROOF SLOPES FROM
 TWO UNITS VERTICAL IN 12 UNITS HORIZONTAL (2:12) AND
 LESS THAN FOUR UNITS VERTICAL IN 12 UNITS HORIZONTAL
 (4:12), DOUBLE UNDERLAYMENT APPLICATION IS REQUIRED.
 - PLEASE ADD NOTE FOR DOUBLE UNDERLAYMENT.
  
 13) 1507.1.1 FBC[B]UNDERLAYMENT. UNLESS OTHERWISE
 NOTED, UNDERLAYMENT FOR ASPHALT SHINGLES, METAL ROOF
 PANELS, METAL ROOF SHINGLES, MINERAL SURFACED ROLL
 ROOFING, SLATE SHINGLES, WOOD SHINGLES, AND WOOD SHAKES
 SHALL CONFORM TO THE APPLICABLE STANDARDS LISTED IN
 THIS CHAPTER. UNDERLAYMENT MATERIALS REQUIRED TO COMPLY
 WITH ASTM D226, D1970, D4869 AND D6757 SHALL BEAR A
 LABEL INDICATING COMPLIANCE TO THE STANDARD DESIGNATION
 AND, IF APPLICABLE, TYPE CLASSIFICATION INDICATED IN
 TABLE 1507.1.1. UNDERLAYMENT SHALL BE APPLIED AND
 ATTACHED IN ACCORDANCE WITH TABLE 1507.1.1.
 - SHEET A4.0 CALLS FOR 15# FELT. PLEASE PROVIDE
 DOCUMENTATION THAT 15# COMPLIES WITH 1507.1.1. OR
 REMOVE NOTE AND SUPPLY UNDERLAYMENT PRODUCT APPROVAL
 WITH ROOFING SUB PERMIT.
  
 14) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS
 FOR ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM
 DEFERRED.
  
 15) PLEASE ADJUST ROOFING WIND DIAGRAMS ON SHEET S-1 TO
 MEET ASCE 7-10 TABLE 30.7.2. TYPICAL ROOF ZONE FOR
 GABLE END WOULD INCLUDE ZONE 2 AT RIDGE. ALSO, TWO ROOF
 TYPES ARE BEING UTILIZED SO ADD SHED ROOF DIAGRAM SINCE
 ZONE 3 HAS UNIQUE REQUIREMENTS.
 - THIS PERMIT IS FOR THE SHED TYPE ROOF, BUT SINCE BOTH
 BUILDING TYPES ARE SHOWN ON PLANS YOU SHOULD SHOW BOTH.
  
 16) 107.5.3 FBC[AMENDED]I FOUND ROOF PITCH ON THE ROOF
 PLAN, BUT IT WOULD BE GOOD TO HAVE THE PITCH SHOWN IN
 ELEVATION OR SECTION AS WELL.
  
 PROVISOS:
 A) DEMOLITION OF STRUCTURES TO BE DONE UNDER SEPARATE
 DEMOLITION PERMIT. IF NOT AVAILABLE AT WEBSITE HTTPS://
 WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-SERVICES/FORMS
 PLEASE REQUEST VIA E-MAIL [email protected]
 B) SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR: SIGNAGE, LIGHT POLES/SITE LIGHTING ,
 LANDSCAPING, IRRIGATION, FENCING AND PAVERS.
 C) SUBMIT TRUSS SHOP DRAWINGS TO THE BUILDING INSPECTOR
 PRIOR TO INSTALLATION. 107.3.4.1 FBC[AMENDED]
 D) DEFERRED SUBMITTALS: PROVIDE PRODUCT APPROVALS FOR
 WNDOWS, DOORS.
 ENGINEERING FOR HANDRAILS AND GUARDRAILS.
 E) NO CERTIFICATE OF OCCUPANCY CAN BE ISSUED FOR THIS
 STRUCTURE UNTIL OCCUPANCY IS DETERMINED AND INTERIOR
 BUILD OUT IS COMPLETE.
 F) CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM
 SAT-SUN
 - NO RESPONSE REQUIRED. THESE WILL BE ADDED TO THE
 PLANS AT FINAL STAMPING.
  
 PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  