Plan Review Notes For Permit 19120499 |
Permit Number |
19120499 |
|
Review Stop |
B |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2020-08-19 07:54:55 | PROVISO = | | 1) WILL NEED TO PROVIDE SIGNED AND SEALED LOUVER SYSTEM | | DETAILS TO COMPLY WITH THE DESIGN WIND LOADS. FBC 1609 | | 2) WILL NEED TO PROVIDE SIGNED AND SEALED METAL CANOPY | | DETAILS TO COMPLY WITH THE DESIGN WIND LOADS. FBC 1609 | | 3) WILL NEED TO PROVIDE A SIGNED AND SEALED SOIL REPORT | | (GEOTECHNICAL REPORT) TO VERIFY THE REQUIRED SOIL | | BEARING CAPACITY PER NOTES ON THE DRAWINGS. |
|