2020-01-30 14:20:33 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| |
| 1. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE, |
| INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF |
| SERVICE IS ADEQUATE. THE LOAD CALCULATION PROVIDED DOES |
| NOT MEET CODE. THE DEMAND FACTORS CANNOT BE APPLIED |
| TWICE. THE CALCULATION PROVIDED APPLIES DEMAND FACTORS |
| TO PANEL K AND THEN USES THAT NUMBER AND APPOIES DEMAND |
| FACTORS AGAIN FOR PANEL MDP. PROVIDE CORRECTION. NEC |
| 215.2, 220, 408.30; FBC RE E3602.2 (IN YOUR RESPONSE |
| LETTER, THIS COMMENT WAS ADDRESSED SATISFACTORILY. |
| HOWEVER, THIS CORRECTION DID NOT MAKE IT ONTO THE PLAN. |
| PROVIDE CORRECTION TO THE PLAN TO MATCH THE EXPLANATION |
| IN THE LETTER.) |
| 2. CORRECTED. |
| 3. CORRECTED. |
| 4. CORRECTED. |
| 5. CORRECTED. |
| 6. CORRECTED. |
| 7. CORRECTED. |
| 8. CORRECTED. |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |