2019-12-22 13:44:12 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE, |
| INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF |
| SERVICE IS ADEQUATE. THE LOAD CALCULATION PROVIDED DOES |
| NOT MEET CODE. THE DEMAND FACTORS CANNOT BE APPLIED |
| TWICE. THE CALCULATION PROVIDED APPLIES DEMAND FACTORS |
| TO PANEL K AND THEN USES THAT NUMBER AND APPOIES DEMAND |
| FACTORS AGAIN FOR PANEL MDP. PROVIDE CORRECTION. NEC |
| 215.2, 220, 408.30; FBC RE E3602.2 |
| 2. PROVIDE ACCURATE LOAD CALCULATION FOR PANEL K, |
| INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF |
| SERVICE IS ADEQUATE. THE LOAD CALCULATION PROVIDED DOES |
| NOT INCLUDE ANY GENERAL LIGHTING LOAD, EVEN THOUGH |
| THESE CIRCUITS ARE SHOWN IN THE PANEL SCHEUDLE. NEC |
| 215.2, 220, 408.30; FBC RE E3602.2 |
| 3. WHAT SIZE IS THE SERVICE TO THIS DWELLING UNIT? THE |
| SIZE IS NOT SPECIFIED ON PLAN. WPB FBC 107.2.1; NEC |
| 215.5, 230, 250.50, 250.94, 408.30; FBC RE E3706.1, |
| E3608.1, E3609.3 |
| 4. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, |
| SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN |
| KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, |
| RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND |
| SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS |
| INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES. |
| SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION. |
| PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902; |
| FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS APPLICABLE. |
| 5. HOW WILL THE INDIVIDUAL CIRCUITS FROM THE EXISTING |
| PANEL BE RELOCATED TO THE NEW PANEL? PLAN IS SILENT IN |
| REGARDS TO THIS. PROVIDE CLARIFICATION. WPB FBC 107.2.1 |
| 6. PLAN DOES NOT STATE WHETHER THE ELECTRICAL SERVICE |
| IS NEW OR EXISTING. IF THIS IS A NEW SERVICE, PROVIDE |
| AVAILABLE SHORT CIRCUIT CALCULATION FOR SERVICE |
| INCLUDING INFORMATION FROM THE POWER COMPANY STATING |
| WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE |
| SERVICE TO CONFIRM THE STATED AIC RATING OF THE SERVICE |
| EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC RE |
| E3606.3 |
| 7. IF NEW SERVICE, OR ANY WORK DONE TO SERVICE, PROVIDE |
| INTERSYSTEM BONDING TERMINATION POINT AT SERVICE. SHOW |
| ON PLAN. NEC 250.94; FBC RE E3609.3 |
| 8. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED |
| PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING |
| ALARMS, OR PROVIDE A NOTE REQUIRING COMPLIANCE. IF NONE |
| ARE EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. |
| FBC RE R314.3, R315.1; WPB FBC 107.2.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| |