2019-12-22 13:44:12CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. THE LOAD CALCULATION PROVIDED DOES
 NOT MEET CODE. THE DEMAND FACTORS CANNOT BE APPLIED
 TWICE. THE CALCULATION PROVIDED APPLIES DEMAND FACTORS
 TO PANEL K AND THEN USES THAT NUMBER AND APPOIES DEMAND
 FACTORS AGAIN FOR PANEL MDP. PROVIDE CORRECTION. NEC
 215.2, 220, 408.30; FBC RE E3602.2
 2. PROVIDE ACCURATE LOAD CALCULATION FOR PANEL K,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. THE LOAD CALCULATION PROVIDED DOES
 NOT INCLUDE ANY GENERAL LIGHTING LOAD, EVEN THOUGH
 THESE CIRCUITS ARE SHOWN IN THE PANEL SCHEUDLE. NEC
 215.2, 220, 408.30; FBC RE E3602.2
 3. WHAT SIZE IS THE SERVICE TO THIS DWELLING UNIT? THE
 SIZE IS NOT SPECIFIED ON PLAN. WPB FBC 107.2.1; NEC
 215.5, 230, 250.50, 250.94, 408.30; FBC RE E3706.1,
 E3608.1, E3609.3
 4. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902;
 FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS APPLICABLE.
 5. HOW WILL THE INDIVIDUAL CIRCUITS FROM THE EXISTING
 PANEL BE RELOCATED TO THE NEW PANEL? PLAN IS SILENT IN
 REGARDS TO THIS. PROVIDE CLARIFICATION. WPB FBC 107.2.1
 6. PLAN DOES NOT STATE WHETHER THE ELECTRICAL SERVICE
 IS NEW OR EXISTING. IF THIS IS A NEW SERVICE, PROVIDE
 AVAILABLE SHORT CIRCUIT CALCULATION FOR SERVICE
 INCLUDING INFORMATION FROM THE POWER COMPANY STATING
 WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE
 SERVICE TO CONFIRM THE STATED AIC RATING OF THE SERVICE
 EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC RE
 E3606.3
 7. IF NEW SERVICE, OR ANY WORK DONE TO SERVICE, PROVIDE
 INTERSYSTEM BONDING TERMINATION POINT AT SERVICE. SHOW
 ON PLAN. NEC 250.94; FBC RE E3609.3
 8. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING
 ALARMS, OR PROVIDE A NOTE REQUIRING COMPLIANCE. IF NONE
 ARE EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS.
 FBC RE R314.3, R315.1; WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER