Plan Review Notes For Permit 19120391 |
Permit Number |
19120391 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2020-03-23 10:25:54 | COMMENTS FROM PREVIOUS REVIEW: | | | | 1) JLRD RESPONSE THAT HEATING AND COOLING CALCULATIONS | | WOULD BE PROVIDED IS NOT SATISFIED AS I DID NOT FIND | | THESE CALCULATIONS IN THE UPLOADED INFORMATION. 2017 | | FLORIDA ENERGY CODE C403.2.1 | | 3) JLRD RESPONSE THAT CX PLAN WILL PROVIDED ONCE CX | | AGENT IS SELECTED NEEDS TO IDENTIFY ON THE MECHANICAL | | DRAWINGS PER 2017 FLORIDA ENERGY CODE C408.2 | | CONSTRUCTION DOCUMENT NOTES SHALL CLEARLY INDICATE | | PROVISIONS FOR COMMISSIONING AND COMPLETION | | REQUIREMENTS IN ACCORDANCE WITH THIS SECTION AND ARE | | PERMITTED TO REFER TO SPECIFICATIONS FOR FURTHER | | REQUIREMENTS. | | | | REVIEWED REMOTELY BY JAMES BAKER, PE | | PX3997, PE77268 | | 561-805-6724 | | | | | | | | | | |
|