2020-01-14 17:06:231ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19120391
 1/14/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEMS- SECTION C403.2.1 FBC EC.
  
 2) SUBMIT AN ENERGY COMPLIANCE REPORT- SEE SECTIONS
 C101.2, C101.5.1 AND C401.2 FBC EC.
  
 3) COMMISSIONING OF THE MECHANICAL SYSTEMS IS REQUIRED
 PER SECTION C408.2 FBC EC. SUBMIT A COMMISSIONING PLAN
 AS OUTLINED IN SECTION C408.2.1 AND DESCRIBED IN
 SECTIONS C403.2.2- C408.2.3.3. PLEASE NOTE THAT A COPY
 OF THE COMMISSIONING REPORT SHALL BE SUBMITTED FOR
 REVIEW AT FINAL INSPECTION.
  
 4) M1 & M2: CORRECT THE M5 REFERENCE FOR THE MECHANICAL
 ROOM TO M2 SECTION 107.2.1 WPB.
  
 5) M1: PROVIDE A DUCT SMOKE DETECTOR SYMBOL IN THE
 SUPPLY SYSTEM OF AHU-1- SECTION 606.2.1 FBC M.
  
 6) M1: SHOW RETURN AIR FROM STORAGE ROOMS 103 & 105-
 SECTION 601.6 FBC M.
  
 7) M1: EXHAUST VENTILATION IS REQUIRED FOR THE DRESSING
 ROOM AT A RATE OF 0.25 CFMS PER SF.- TABLE 403.3.1.1
 FBC M.
  
 8) M2: THE VENTILATION CALCULATIONS FOR AUDITORIUM ARE
 INCORRECT. TABLE 403.3.1.1 FBC M REQUIRES 150 PERSONS
 PER 1000 SF.
  
 9) PROVIDE ENGINEERING FOR INSTALLATION OF THE CHILLER-
 SECTION 301.15 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  