Plan Review Notes
Plan Review Notes For Permit 19120391
Permit Number 19120391
Review Stop B
Sequence Number 1
Notes
Date Text
2020-01-28 12:54:082017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19120391
 ADD: 4850 FRED GLADSTONE DR.
 CONT: THE WHITING-TURNER CO.
 TEL: 954-536-9251
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 1ST REVIEW
 DATE: TUES. JAN. 28TH/2020
 ACTION: DENIED
  
 1) ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH
 ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES
 TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH
 THE PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/14, AND
 THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR
 GREATER THAN $750,000 WILL NEED TO COMPLY WITH THIS
 ORDINANCE. PER CITY OF WEST PALM BEACH ORDINANCE NO.
 4504-14, AND CITY OF WEST PALM BEACH CODE OF
 ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION
 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS
 1% OF THE TOTAL PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE
 DEVELOPMENT.
 (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND
 THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL
 PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW
 CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN
 EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS
 WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED
 CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES
 REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED
 SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF
 THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW
 CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 2) THE PERMIT APPLICATION INDICATES THE DOLLAR AMOUNT
 OF $2,500,000.00 DOLLARS IN VALUE. THIS MAIN BUILDING
 PERMIT WILL INCLUDE THE FEES FOR THE MECHANICAL,
 ELECTRICAL, PLUMBING & ROOFING PERMITS. WHEN THE
 GENERAL CONTRACTOR COMES IN FOR A BUILDING PERMIT WITH
 THE SIGNED PERMIT APPLICATION FORM BY THE QUALIFIER AND
 OWNER AND BRINGS IN THE LISTED SUB-PERMITS M-E-P &
 ROOFING PERMITS SIGNED BY THE QUALIFIER OF EACH
 COMPANY, THEIR INSURANCES AND LICENSURE UP TO DATE, THE
 M-E-P AND ROOFING PERMITS ARE FREE OF CHARGE. IF THE
 M-E-P & ROOFING PERMITS COME IN LATER THERE WILL BE AN
 $80.00 ADMINISTRATIVE FEE FOR EACH PERMIT.
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 3) THIS BUILDING DOES NOT QUALIFY AS A THRESHOLD
 BUILDING BUT COULD BE CONSIDERED FOR THE RESIDENT
 INSPECTOR PROGRAM UNDER SECTION 110.3.9 OF THE WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, 6TH
 EDITION (2017) CHAPTER 1, ADMINISTRATION CODE. THE
 ALTERNATIVE IS USING THE CITY INSPECTORS FOR
 INSPECTIONS, I?VE SPOKEN KEN CONRAD CHIEF BUILDING
 INSPECTOR IF HE HAD ANY PREFERENCE. IF THE CONTRACTOR
 WAS PUSHED WITH MULTIPLE BUILDING INSPECTIONS EACH DAY
 BECAUSE OF TIME CONSTRAINTS THE RESIDENT INSPECTOR
 MAYBE PREFERRED. IF YOU WOULD PREFER TO USE THE CITY
 INSPECTORS FOR THE STRUCTURAL PORTION OF THE BUILDING
 PLEASE REVIEW THE LIMITATIONS OF OUR STAFF FOR WELDED
 OR BOLTED CONNECTIONS.
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE
 AMERICAN WELDING SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
 FOR THESE TYPES OF CONNECTIONS A 3RD PARTY
 CERTIFICATION WOULD BE REQUIRED. IF THERE IS ANY
 QUESTIONS ABOUT THE CODE REQUIREMENTS FOR THIS SECTION,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666. PLEASE LET US KNOW YOUR INTENTIONS, IF
 YOU DECIDE TO USE A RESIDENT INSPECTOR WE WILL SEND THE
 FORMS TO YOU BY E-MAIL, WE JUST NEED TO KNOW YOUR
 INTENTIONS. THANK YOU.
  
 4) SHEET S-3 UNDER THE HEADING FOUNDATION NOTE 1.A
 INDICATES THERE IS A SOILS REPORT DATED 08/14/19 BY
 TERRACON. IF THEY CAN UPLOAD THE REPORT WITH ELECTRONIC
 SIGNATURES WITH THE NEXT SUBMITTAL GREAT. IF THEY NEED
 TO SUBMIT PAPER REPORT WITH ORIGINAL SIGNATURE AND SEAL
 THAT WILL WORK ALSO. 2017 FBC-B 1803.5.2 QUESTIONABLE
 SOIL. WHERE THE CLASSIFICATION, STRENGTH OR
 COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR WHERE A
 LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE
 PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION
 BE CONDUCTED.
  
 5) NO ACTION REQUIRED. SHEET S-4 WIND PRESSURES ARE
 GOOD FOR ROOF ZONES FOR FLAT 1,2,3, SLOPED 6,7,8 AND
 WALL ZONES 4 & 5.
  
 6) THIS REVIEW THERE WERE NO PRODUCT APPROVALS
 SUBMITTED. IF EITHER THE DESIGNER OF RECORD OR THE
 GENERAL CONTRACTOR WOULD PREFER TO HAVE THE BAR JOIST &
 PRODUCT APPROVAL FOR COMPONENTS AND CLADDING DEFERRED
 PLEASE NOTE SO FOR THE NEXT SUBMITTAL. 107.3.4.2
 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION,
 DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF
 THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 6A) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STANDS
  
 6B) IDENTIFY GLAZING/ MULLIONS. THE SUBMITTED PRODUCT
 APPROVALS THE ELEMENTS LISTED BELOW ARE NOT IDENTIFIED.
 PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 6C) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 7) ON BOTH ARCHITECTURAL SHEETS A-5.2 & A-5.3 AND THE
 STRUCTURAL SHEETS S-6, S-7 & S-8 ALL SLOPED ROOF
 SECTIONS SHOW THE USE OF 5/8 INCH CDX PLYWOOD. PLEASE
 REFER BACK TO THE 2017 FBC-B SECTION 603.1.1.1.3 ROOF
 CONSTRUCTION INCLUDING GIRDERS, TRUSSES FRAMING &
 DECKING NEED TO BE FIRE-RETARDANT TREATED WOOD. THIS IS
 FOR BOTH TYPE I & TYPE II CONSTRUCTION. SECTION 718.5
 FOR CONCEALED SPACES, EXCEPTION 1 REFERS BACK TO
 COMBUSTIBLE MATERIALS IN ACCORDANCE WITH SECTION 603.
  
 8) SHEET A-5.2 WALL SECTION B, THE LIFE SAFETY SHEET
 DECLARES THIS SECTION OF THE ADDITION AS TYPE I-B
 CONSTRUCTION. IN THE 2017 FBC-B TABLE 601 FOR TYPE I-B
 CONSTRUCTION, THE ROOF CONSTRUCTION AND ASSOCIATED
 SECONDARY MEMBERS REQUIRES A 1 HOUR FIRE RATING OF THE
 LIGHT GAUGE METAL TRUSSES BEING INSTALLED IN THIS AREA.
  
 9) SHEET A-5.2 WALL SECTION B HAS A NOTE FOR THE 2 HOUR
 RATED CEILING SEE A-9.0 DETAIL # 5. THIS DETAIL IS FOR
 A 2 HOUR FIRE RATED SHAFT WALL DESIGN, UL DESIGN U-415
 SYSTEM B. THIS SYSTEM U-415 IS A TESTED WALL ASSEMBLY,
 TO BE USED VERTICALLY, THAT IS HOW IT WAS TESTED. YOU
 WILL NEED TO FIND A CEILING ASSEMBLY WITH A 2 HOUR FIRE
 RATING.
  
 10) SHEET A-5.2 DETAIL B INDICATES THE INSTALLATION OF
 ICYNENE SPRAY INSULATION. PLEASE SUBMIT THE ICC-ES OR
 ERS REPORT AND CIRCLE WHICH APPLICATION WILL BE USED
 SEE 4.0 DESIGN AND INSTALLATION. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED. SHOW COMPLIANCE WITH
 2603.4.1.6 ATTICS, THE FOAM INSULATION SHALL BE
 PROTECTED AGAINST IGNITION. THIS BARRIER IS TO COVER
 THE FOAM INSULATION.
  
 11) SHEET A-1.0 SHOWS THE STAGE 1 FOOT HIGHER THAN THE
 FLOOR AUDITORIUM. IT APPEARS IN THE DETAIL 7/ A-8.1 THE
 STAGE IS CONCRETE BASED. NEITHER THE ARCHITECTURAL NOR
 STRUCTURAL SHEETS PROVIDE THE HEIGHT OF THE MID-LANDING
 OF THE ACCESSIBLE RAMP. 2017 FBC-ACCESSIBILITY CODE
 SECTION 405.2. RAMP RUNS SHALL HAVE A SLOPE NOT STEEPER
 THAN 1:12.
  
 12) SHEET A-1. SHOWS A DETAIL 3A & 3B /A-6.3 PANTRY
 WALL 104 WITH A MICROWAVE ON A SHELF. THE TOP OF THE
 SHELF IS AT 48 INCHES ABOVE THE FLOOR. MUST COMPLY WITH
 THE 2017 ACCESSIBILITY CODE SECTIONS:
  
 12A) 308 REACH RANGES. 308.2 FORWARD REACH. / 308.2.1
 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH. 308.3 SIDE
 REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 OBSTRUCTED HIGH
 REACH.
  
 12B) 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS
 SHALL BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL
 BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT
 GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE
 REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS
 MAXIMUM.
  
 13) THIS REVIEW CYCLE THERE WAS NO ENERGY CODE REPORTS
 SUBMITTED. 2017 FBC-ENERGY CODE. C401.2 APPLICATION.
 COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE
 FOLLOWING:
 1.THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1, EXCLUDING
 SECTION 9.4.1.1(G) OF THE STANDARD.
 2.THE REQUIREMENTS OF SECTIONS C402 THROUGH C405. IN
 ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY WITH
 SECTION C406 AND TENANT SPACES SHALL COMPLY WITH
 SECTION C406.1.1.
 3.THE REQUIREMENTS OF SECTIONS C402.5, C403.2, C404,
 C405.2, C405.3, C405.5, C405.6 AND C407. THE BUILDING
 ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 PERCENT
 OF THE STANDARD REFERENCE DESIGN BUILDING.
  
 14) - DIGITAL SUBMITTALS: PLANS WILL BE REVIEWED BY THE
 PBC IMPACT FEE OFFICE DIGITALLY VIA PROJECT DOX UPON
 NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR
 WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE
 WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY
 UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE. THE FORM CAN BE FOUND AT:
 HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  
 15) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  