Plan Review Notes For Permit 19120390 |
Permit Number |
19120390 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-12-16 09:04:53 | BUILDING REVIEW COMMENTS: | | | | W.P.B. PERMIT: 19120390 | | REVIEWED: DECEMBER 16, 2019 | | | | DYLAN BATTLES | | BUILDING PLANS EXAMINER PX4191 | | [email protected] | | 561-805-6718 | | | | FLORIDA BUILDING CODE,6TH EDITION (2017) | | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK | | BELOW) | | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ | | BUILDING-PERMIT-FORMS | | FBC[EXISTING] = FBC EXISTING BUILDING | | FBC[R] = FBC RESIDENTIAL | | | | NOA 18-0919.12 FOR FLAT ROOF | | FASTENING OPTION #2 WAS SELECTED AND THAT OPTION IS FOR | | MAXIMUM PRESSURE OF -45 FOR ALL 3 ROOF ZONES. | | THAT WILL NOT PROVIDE MAXIMUM PRESSURE ON ROOF ZONE 3 | | AND LIMITATION #9 APPLIES. THAT LIMITATION STATES THAT | | ENHANCED NAILING DOES NOT APPLY TO FASTENING OPTION #2. | | PLEASE SELECT A SYSTEM WHERE MAXIMUM DESIGN PRESSURE | | COVERS ALL 3 ZONES, OR SELECT SYSTEM THAT ALLOWS | | ENHANCED NAILING AND SUPPLY ENGINEERED LETTER TO SHOW | | THE SPACING. | | | | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F | | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME | | [email protected] | | | | | | |
|