2019-12-16 09:04:53BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19120390
 REVIEWED: DECEMBER 16, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[R] = FBC RESIDENTIAL
  
 NOA 18-0919.12 FOR FLAT ROOF
 FASTENING OPTION #2 WAS SELECTED AND THAT OPTION IS FOR
 MAXIMUM PRESSURE OF -45 FOR ALL 3 ROOF ZONES.
 THAT WILL NOT PROVIDE MAXIMUM PRESSURE ON ROOF ZONE 3
 AND LIMITATION #9 APPLIES. THAT LIMITATION STATES THAT
 ENHANCED NAILING DOES NOT APPLY TO FASTENING OPTION #2.
 PLEASE SELECT A SYSTEM WHERE MAXIMUM DESIGN PRESSURE
 COVERS ALL 3 ZONES, OR SELECT SYSTEM THAT ALLOWS
 ENHANCED NAILING AND SUPPLY ENGINEERED LETTER TO SHOW
 THE SPACING.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  